Thomson Power Systems · TS840 Series (Agriculture/Light Industrial)
New
Thomson TS840 Automatic Transfer Switch
Automatic Transfer Switches
Agriculture and light-industrial automatic transfer switch. 100-800A, open transition, mechanically interlocked switching, TSC 80 controller. UL 1008 listed.
The Thomson TS840 is a mechanically-interlocked automatic transfer switch built for agriculture, telecom, and light-industrial standby power applications. Available from 100A to 800A in single-phase and three-phase configurations, it uses a heavy-duty brushless gear-motor mechanism with fully enclosed silver alloy contacts rated for 3-cycle short circuit withstand at 65,000A (240V) with circuit breaker protection, or 100,000A with fuse protection.
The TS840 ships standard in a NEMA 3R outdoor enclosure, making it suitable for exposed installations common in agricultural and telecom site deployments. The TSC 80 microprocessor controller handles all automatic transfer functions including engine start signaling, voltage and frequency monitoring, and programmable time delays. A service-entrance rated (SE) variant is available for installations requiring the ATS to serve as the main disconnect. The operating temperature range spans -40°C to 50°C.
The TS840 occupies the entry tier of Thomson's mechanically-held ATS lineup, positioned below the TS870 (commercial/industrial) and TS880 (mission critical). Its defining characteristics:
NEMA 3R standard — most Thomson ATS models default to NEMA 1 indoor; the TS840 defaults to outdoor, reflecting its target deployments
TSC 80 controller — provides the essentials (timers, voltage sensing, exercise scheduling) without the LCD display, Modbus, or programmable I/O of the TSC 7320 used on the TS870
Open transition only — no closed-transition option; applications that need sub-100ms transfers should step up to the TS870
Typical installations: agricultural irrigation pumps, dairy/poultry operations, cell towers, rural telecom huts, and small industrial buildings without critical-continuity requirements.
In Northern California agriculture and telecom, we see the TS840 most commonly in the 200-400A range on dairy operations and cell tower sites. The mechanically-held mechanism is well-suited to infrequent transfers — these units might only operate a few times per year during grid outages, and the gear-motor mechanism tolerates long idle periods better than contactors that can develop coil issues from disuse.
The TSC 80 controller is straightforward to program in the field; the optional SDM LCD display module makes timer adjustments easier than the base LED interface.
Frequently Asked Questions
What applications is the Thomson TS840 designed for?
The TS840 is specifically designed for agriculture, telecommunications, and light-industrial standby applications. It uses a heavy-duty brushless gear-motor mechanism with mechanical interlocking between utility and generator switching units, providing reliable open-transition transfer in environments where simplicity and durability are priorities. The standard NEMA 3R outdoor enclosure makes it suitable for exposed installations without additional weather protection.
What amperage ratings are available for the TS840?
The TS840 is available in 100A, 150A, 200A, 250A, 400A, 600A, and 800A ratings. Single-phase units (2-pole) are available at 120/240V, while three-phase units (3-pole) support 120/208V and 120/240V systems. All ratings carry 100% continuous current capacity for all load types. A service-entrance rated (SE) variant is also available.
What controller does the TS840 use?
The TS840 uses the TSC 80 microprocessor-based controller for voltage sensing, frequency monitoring, and timing functions. It includes programmable timers for engine start delay (0-60 sec), engine warm-up, cool-down (0-30 min), neutral position delay (0-60 sec), and utility return (0-30 min), plus a fixed 30-minute exercise timer. An optional SDM LCD display module is available for field adjustments.
What are the short circuit withstand ratings?
The TS840 is rated for 3-cycle short circuit current withstand. At 240V, the withstand rating is 65,000A with upstream circuit breaker protection. With upstream fuse protection (Type T or J), the rating increases to 100,000A for the 100-600A frames. The 800A frame fuse rating requires factory consultation.
How does the TS840 compare to the TS870?
The TS840 is Thomson's entry-level mechanically-held ATS for simpler applications, while the TS870 is the commercial/industrial workhorse. Key differences: the TS840 tops out at 800A while the TS870 goes to 1200A; the TS840 is open-transition only while the TS870 offers optional closed-transition and bypass-isolation; the TS840 uses the simpler TSC 80 controller while the TS870 uses the advanced TSC 7320 with LCD display and Modbus; and the TS840 ships in NEMA 3R outdoor enclosure by default while the TS870 defaults to NEMA 1 indoor.
What are the physical dimensions?
Dimensions vary by frame (NEMA 3R enclosure): 100-200A is 31.1 x 22.3 x 14 inches (143 lbs); 250A is 35.1 x 27.3 x 14 inches (172 lbs); 400A is 43.1 x 34.3 x 13 inches (227 lbs); 600A is 46.1 x 36.3 x 14.5 inches (248 lbs); 800A is 48.1 x 37.8 x 18 inches (309 lbs). Distribution breaker variants are larger.
Key Terms
Open-transition transfer
A brief (typically 100-500ms) interruption between disconnecting from one source and connecting to the other. Standard for agricultural and light-industrial backup where momentary outage is acceptable.
Mechanically-held switching
Switch positions are maintained by a mechanical latch mechanism driven by a brushless gear-motor, as opposed to contactor-style switches held by an electromagnetic coil. More robust for infrequent operations and harsh environments.
NEMA 3R enclosure
Outdoor-rated enclosure providing protection against rain, sleet, and external ice formation. Standard on the TS840 for agricultural and outdoor telecom installations.
TSC 80 controller
Thomson's basic microprocessor-based ATS controller with status LEDs, programmable timers, exercise scheduling, and an isolation plug for disconnecting control circuits. Optional SDM LCD display module available for field adjustments.
Found in these gensets
Generator models that ship with or are commonly paired with the Thomson TS840 Automatic Transfer Switch.
Blue Star Power Systems
Blue Star GM100-03
100 kW standby · Natural Gas / LPG · Liquid-cooled
100 kW natural gas standby for commercial, school, and multi-family buildings where gas-fueled backup and component independence matter.
100 kW natural gas standby generator (80 kW on LP) from Blue Star Power Systems. PSI 5.7LTCAC turbocharged charge-air-cooled V8, UCI274C alternator, DCP7310 controller, 208-600V output.
3-phasecommercialmedium-commercial
Blue Star Power Systems
Blue Star GM50-03
50 kW standby · Natural Gas / LPG · Liquid-cooled
50 kW natural gas standby for light commercial, retail, and small office buildings where gas-fueled backup and component independence matter.
50 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 5.7L eight-cylinder naturally aspirated V8 engine, UCI224D alternator, DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star GM60-02
60 kW standby · Natural Gas / LPG · Liquid-cooled
60 kW natural gas standby for light commercial, retail, and small facilities where gas-fueled backup and component independence matter.
60 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 5.7L eight-cylinder naturally aspirated V8 engine, UCI224E alternator, DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star GM60-02P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
55 kW prime natural gas for continuous-duty commercial applications, cogeneration sites, and facilities needing 24/7 gas-fueled power.
55 kW prime natural gas / LP generator from Blue Star Power Systems. PSI 5.7L eight-cylinder V8 with catalyst/silencer, UCI224E alternator, DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star JD100-01
100 kW standby · Diesel · Liquid-cooled
100 kW diesel standby for commercial, multi-family, and municipal facilities where value engineering and service-tech independence matter.
100 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045HF285 engine, UCI274 alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star JD150-01
150 kW standby · Diesel · Liquid-cooled
150 kW diesel standby for commercial, institutional, and municipal facilities where value engineering and component independence matter.
150 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6068HF285 6-cylinder engine, UCI274/UCDI274 alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star JD200-01
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for value-engineering projects, municipal facilities, and service-savvy buyers who prioritize component independence.
200 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6068HFG85 6-cylinder engine, S4L1S/UCDI274 alternator, DCP7310 controller.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star JD250-02
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for commercial, institutional, and campus facilities where value engineering and non-proprietary component access matter.
250 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6090HF484 9.0L engine, S4L1S/S4L1D alternator, DCP7310 controller.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star JD275-02
275 kW standby · Diesel · Liquid-cooled
275 kW diesel standby for commercial, campus, and institutional facilities where value engineering and non-proprietary component access matter.
275 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6090HF484 9.0L 6-cylinder engine, S4L1S alternator, DCP7310 controller. Three-phase only.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star JD300-02
300 kW standby · Diesel · Liquid-cooled
300 kW diesel standby for large commercial, campus, and municipal facilities where value engineering and non-proprietary component access matter.
300 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6090HFG86 9.0L 6-cylinder engine, S4L1D alternator, DCP7310 controller. Three-phase only.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star JD40-03
40 kW standby · Diesel · Liquid-cooled
40 kW diesel standby for small commercial, retail, and light-duty facilities where component independence and value engineering matter.
40 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045TF280 engine, UCI224 alternator, DCP7310 controller.
Tier 33-phaselight-commercialsmall-office
Blue Star Power Systems
Blue Star JD40-05FT4
40 kW standby · Diesel · Liquid-cooled
40 kW Tier 4 Final diesel standby for small commercial and light-duty facilities requiring current emissions compliance.
40 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. John Deere 3029HG530 2.9L inline-three with DOC/DPF, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommercialsmall-commercial
Blue Star Power Systems
Blue Star JD40-05FT4MP
40 kW standby · Diesel · Liquid-cooled
40 kW Tier 4 Final mobile diesel for construction sites, emergency response, and temporary power where portability and clean emissions matter.
40 kW Tier 4 Final mobile trailer diesel generator built by Blue Star Power Systems. John Deere 3029HG530 three-cylinder engine, UCI224D alternator, DCP7310 controller, 130-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star JD50-03
50 kW standby · Diesel · Liquid-cooled
50 kW diesel standby for small commercial, retail, worship, and light-industrial sites prioritizing component independence over brand premium.
50 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045TF280 engine, UCI224 alternator, DCP7310 controller.
Tier 33-phaselight-commercialsmall-office
Blue Star Power Systems
Blue Star JD60-02
60 kW standby · Diesel · Liquid-cooled
60 kW diesel standby for light commercial, retail, multi-family, and telecom sites where value engineering and open-source components matter.
60 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045TF280 engine, UCI224 alternator, DCP7310 controller.
Tier 33-phaselight-commercialsmall-office
Blue Star Power Systems
Blue Star JD60-04FT4
60 kW standby · Diesel · Liquid-cooled
60 kW Tier 4 Final diesel standby for commercial and light-industrial facilities requiring current emissions compliance and component independence.
60 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. John Deere 4045HFG04 4.5L inline-four with SCR/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommercialsmall-commercial
Blue Star Power Systems
Blue Star JD60-04FT4MP
60 kW standby · Diesel · Liquid-cooled
60 kW Tier 4 Final mobile diesel for construction sites, emergency response, and temporary power where portability and clean emissions matter.
60 kW Tier 4 Final mobile trailer diesel generator built by Blue Star Power Systems. John Deere 4045HFG04 four-cylinder engine, UCI224F alternator, DCP7310 controller, 250-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star JD80-02
80 kW standby · Diesel · Liquid-cooled
80 kW diesel standby for commercial, multi-family, and municipal facilities where value engineering and service-tech independence matter.
80 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045HF285 engine with charge air cooling, UCI274/UCI224 alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star JD80-03FT4
80 kW standby · Diesel · Liquid-cooled
80 kW Tier 4 Final diesel standby for commercial, multi-family, and institutional facilities requiring current emissions and component independence.
80 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. John Deere 4045HFG04 4.5L inline-four with SCR/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommercialsmall-commercial
Blue Star Power Systems
Blue Star JD80-03FT4MP
80 kW standby · Diesel · Liquid-cooled
80 kW Tier 4 Final mobile diesel for construction, emergency response, and planned outage support where portability and clean emissions matter.
80 kW Tier 4 Final mobile trailer diesel generator built by Blue Star Power Systems. John Deere 4045HFG04 four-cylinder engine, UCI274C alternator, DCP7310 controller, 250-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star NG150-01
150 kW standby · Natural Gas / LPG · Liquid-cooled
150 kW natural gas standby for commercial, institutional, and campus buildings where gas-fueled backup and component independence matter.
150 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.1LT turbocharged inline-six, DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star NG150-01P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
125 kW prime natural gas for continuous-duty commercial and institutional applications needing 24/7 gas-fueled power with component independence.
125 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 8.1LT inline-six, DCP7310 controller, 208-600V, continuous prime duty.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star NG200-01
200 kW standby · Natural Gas / LPG · Liquid-cooled
200 kW natural gas standby for commercial, institutional, and campus buildings where gas-fueled backup and component independence matter.
200 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 11.1L turbocharged inline-six, DCP7310 controller, 208-600V output.
3-phasecommercialmedium-commercial
Blue Star Power Systems
Blue Star NG200-01P
200 kW standby · Natural Gas / LPG · Liquid-cooled
175 kW prime natural gas for continuous-duty commercial and institutional applications needing 24/7 gas-fueled power with component independence.
175 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 11.1L inline-six, DCP7310 controller, 208-600V, continuous prime duty.
3-phasecommercialmedium-commercial
Blue Star Power Systems
Blue Star NG265-01
265 kW standby · Natural Gas / LPG · Liquid-cooled
265 kW natural gas standby for large commercial, campus, and hospital (non-critical) facilities where gas-fueled backup matters.
265 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 14.6L turbocharged V8, DCP7310 controller, structural steel base, 208-600V.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG265-01P
265 kW standby · Natural Gas / LPG · Liquid-cooled
250 kW prime natural gas for continuous-duty commercial, CHP, and campus applications needing 24/7 gas-fueled power.
250 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 14.6L V8, DCP7310 controller, structural steel base, continuous prime duty.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG300-01
300 kW standby · Natural Gas / LPG · Liquid-cooled
300 kW natural gas standby for large commercial, campus, and institutional facilities where gas-fueled backup and component independence matter.
300 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 14.6L turbocharged V8, DCP7310 controller, structural steel base, three-phase 208-600V.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG300-01P
300 kW standby · Natural Gas / LPG · Liquid-cooled
260 kW prime natural gas for continuous-duty commercial, CHP, and campus applications needing 24/7 gas-fueled power.
260 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 14.6L V8, DCP7310 controller, structural steel base, three-phase 208-600V.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG350-02
350 kW standby · Natural Gas · Liquid-cooled
350 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
350 kW natural gas standby generator from Blue Star Power Systems. PSI 14.6LHO high-output V8, DCP7310 controller, structural steel base, three-phase 208-600V. Natural gas only — no LP rating.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG400-01
400 kW standby · Natural Gas / LPG · Liquid-cooled
400 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
400 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L turbocharged V12, DCP7310 controller, structural steel base, three-phase 208-600V.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG400-01P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
375 kW prime natural gas for continuous-duty commercial, CHP, and campus applications needing 24/7 gas-fueled power.
375 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 21.9L V12, DCP7310 controller, structural steel base, three-phase 208-600V.
3-phaselarge-commercialhotel
Blue Star Power Systems
Blue Star NG425-01
425 kW standby · Natural Gas / LPG · Liquid-cooled
425 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
425 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG450-01
450 kW standby · Natural Gas / LPG · Liquid-cooled
450 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
450 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG500-01
500 kW standby · Natural Gas / LPG · Liquid-cooled
500 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
500 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG500-01P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
450 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power.
450 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG500-02
500 kW standby · Natural Gas · Liquid-cooled
500 kW natural-gas-only standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
500 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 21.9LHO V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V. LP not available.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star PD100-01
100 kW standby · Diesel · Liquid-cooled
100 kW diesel standby for commercial, institutional, and municipal facilities where Perkins parts access and non-proprietary components matter.
100 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1104D-E44TAG2 turbocharged intercooled engine, UCI274C alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD125-01
125 kW standby · Diesel · Liquid-cooled
125 kW diesel standby for commercial, institutional, and municipal facilities where Perkins parts access and component independence matter.
125 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG2 six-cylinder engine with charge air cooling, UCI274E alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD150-01
150 kW standby · Diesel · Liquid-cooled
150 kW diesel standby for commercial, institutional, and municipal facilities where value engineering and Perkins global parts access matter.
150 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG2 six-cylinder engine with charge air cooling, UCI274F alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD180-01
180 kW standby · Diesel · Liquid-cooled
180 kW diesel standby for commercial, institutional, and municipal facilities where value engineering and Perkins global parts access matter.
180 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG4 six-cylinder engine with charge air cooling, UCI274G alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD200-01
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for value-engineering projects, municipal facilities, and service-savvy buyers who prioritize component independence.
200 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG5 six-cylinder engine with charge air cooling, UCI274H alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD250-01
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for large commercial, campus, and industrial facilities where value engineering and non-proprietary component access matter.
250 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1706D-E93TAG1 six-cylinder engine with charge air cooling, S4L1D-C41 alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD300-01
300 kW standby · Diesel · Liquid-cooled
300 kW diesel standby for large commercial, campus, and industrial facilities where value engineering and non-proprietary component access matter.
300 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1706D-E93TAG2 six-cylinder engine with charge air cooling, S4L1D-D41 alternator, DCP7310 controller.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star PD350-01
350 kW standby · Diesel · Liquid-cooled
350 kW diesel standby for large commercial, industrial, and campus facilities where Perkins parts access and component independence matter.
350 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 2206D-E13TAG2 six-cylinder engine with charge air cooling, S4L1D-E41 alternator, DSE DCP7310 controller.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star PD400-01
400 kW standby · Diesel · Liquid-cooled
400 kW diesel standby for industrial, campus, and data center facilities where value engineering and non-proprietary component access matter.
400 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 2206D-E13TAG3 six-cylinder engine with charge air cooling, S4L1D-F41 alternator, DSE DCP7310 controller.
Tier 33-phasecommerciallight-industrial
Blue Star Power Systems
Blue Star PD450-01
450 kW standby · Diesel · Liquid-cooled
450 kW diesel standby for industrial, campus, and data center facilities where value engineering and open-architecture components matter.
450 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 2506D-E15TAG1 six-cylinder engine with charge air cooling, HCI534C alternator, DSE DCP7310 controller.
Tier 33-phasecommercialindustrial
Blue Star Power Systems
Blue Star PD50-01
50 kW standby · Diesel · Liquid-cooled
50 kW diesel standby for small commercial, worship, and light-industrial sites prioritizing Perkins global parts availability and value engineering.
50 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1104D-44TG1 turbocharged engine, UCI224D alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD500-01
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for industrial, data center, and campus facilities where value engineering and non-proprietary component access matter.
500 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2506C-E15TAG3 six-cylinder engine with charge air cooling, HCI534D alternator, DSE DCP7310 controller.
Tier 23-phasecommercialindustrial
Blue Star Power Systems
Blue Star PD60-01
60 kW standby · Diesel · Liquid-cooled
60 kW diesel standby for light commercial, retail, and multi-family sites where Perkins global parts network and component independence matter.
60 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1104D-E44TG1 turbocharged engine, UCI224E alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PD80-01
80 kW standby · Diesel · Liquid-cooled
80 kW diesel standby for commercial, multi-family, and municipal sites where Perkins global parts availability and value engineering matter.
80 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1104D-E44TAG2 turbocharged intercooled engine, UCI224G alternator, DCP7310 controller.
Tier 33-phaselight-commercialcommercial
Blue Star Power Systems
Blue Star PS130-01
130 kW standby · Natural Gas / LPG · Liquid-cooled
130 kW natural gas standby for commercial, school, and multi-family buildings where gas-fueled backup and component independence matter.
130 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.8LTCAC turbocharged V8, DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star PS150-01
150 kW standby · Natural Gas / LPG · Liquid-cooled
150 kW natural gas standby for commercial, school, and institutional buildings where gas-fueled backup and component independence matter.
150 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.8LTCAC turbocharged-aftercooled V8, DCP7310 controller, single- and three-phase 120-600V.
3-phaselarge-commercialschool-campus
Blue Star Power Systems
Blue Star PS40-01
40 kW standby · Natural Gas / LPG · Liquid-cooled
40 kW natural gas standby for light commercial, retail, and small facilities where gas-fueled backup and component independence matter.
40 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 4.3L six-cylinder naturally aspirated V6 engine, UCI224C alternator, DSE DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star PS40-01P
40 kW standby · Natural Gas / LPG · Liquid-cooled
35 kW prime natural gas for continuous-duty commercial applications and facilities needing 24/7 gas-fueled power with component independence.
35 kW prime natural gas / LP generator from Blue Star Power Systems. PSI 4.3L six-cylinder V6 engine with catalyst/silencer, UCI224C alternator, DSE DCP7310 controller, 208-600V output.
3-phasecommerciallight-commercial
Blue Star Power Systems
Blue Star VD100-04FT4
100 kW standby · Diesel · Liquid-cooled
100 kW Tier 4 Final diesel standby for commercial and institutional facilities requiring current emissions compliance and component independence.
100 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD581VE 5.13L inline-four with SCR/DPF/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommercialsmall-commercial
Blue Star Power Systems
Blue Star VD100-04FT4MP
100 kW standby · Diesel · Liquid-cooled
100 kW Tier 4 Final mobile diesel for construction, emergency response, and temporary power where portability and clean emissions matter.
100 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD581VE four-cylinder engine, UCI274D alternator, DCP7310 controller, 250-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD125-04FT4
125 kW standby · Diesel · Liquid-cooled
125 kW Tier 4 Final diesel standby for commercial and institutional facilities requiring current emissions compliance and component independence.
125 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD582VE 5.13L inline-four with SCR/DPF/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommercialsmall-commercial
Blue Star Power Systems
Blue Star VD125-04FT4MP
125 kW standby · Diesel · Liquid-cooled
125 kW Tier 4 Final mobile diesel for construction, emergency response, and temporary power where portability and clean emissions matter.
125 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD582VE four-cylinder engine, UCI274E alternator, DCP7310 controller, 250-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD150-04FT4
150 kW standby · Diesel · Liquid-cooled
150 kW Tier 4 Final diesel standby for commercial, institutional, and municipal facilities requiring current emissions and component independence.
150 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD881VE 7.7L inline-six with SCR/DPF/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD150-04FT4MP
150 kW standby · Diesel · Liquid-cooled
150 kW Tier 4 Final mobile diesel for construction, planned outage support, and temporary power requiring portability and clean emissions.
150 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD881VE six-cylinder engine, UCI274F alternator, DCP7310 controller, 250-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD200-04FT4
200 kW standby · Diesel · Liquid-cooled
200 kW Tier 4 Final diesel standby for commercial, institutional, and campus facilities requiring current emissions and component independence.
200 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD1180VE 10.8L inline-six with SCR/DPF/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD200-04FT4MP
200 kW standby · Diesel · Liquid-cooled
200 kW Tier 4 Final mobile diesel for construction, planned outage support, and temporary power requiring portability and clean emissions.
200 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD1180VE six-cylinder engine, UCDI274J1 alternator, DCP7310 controller, 350-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD230-01
230 kW standby · Diesel · Liquid-cooled
230 kW diesel standby for commercial, institutional, and campus facilities where value engineering and non-proprietary component access matter.
230 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD851GE 7.7L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD250-03
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for large commercial, campus, and institutional facilities where value engineering and non-proprietary component access matter.
250 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD852GE 7.7L inline-six, DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD250-04FT4
250 kW standby · Diesel · Liquid-cooled
250 kW Tier 4 Final diesel standby for commercial, campus, and institutional facilities requiring current emissions and component independence.
250 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD1381VE 12.8L inline-six with SCR/DPF/DOC, DCP7310 controller, 208-600V.
Tier 4 Final3-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD250-04FT4MP
250 kW standby · Diesel · Liquid-cooled
250 kW Tier 4 Final mobile diesel for construction, planned outage support, and large-scale temporary power with clean emissions.
250 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD1381VE six-cylinder engine, S4L1D-D41 alternator, DCP7310 controller, 350-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD275-01
275 kW standby · Diesel · Liquid-cooled
275 kW diesel standby for large commercial, campus, and institutional facilities where value engineering and non-proprietary component access matter.
275 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD853GE 7.7L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD300-01
300 kW standby · Diesel · Liquid-cooled
300 kW diesel standby for large commercial, campus, and industrial facilities where value engineering and non-proprietary component access matter.
300 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1351GE 12.8L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD300-04FT4
300 kW standby · Diesel · Liquid-cooled
300 kW Tier 4 Final diesel standby for large commercial, campus, and industrial facilities requiring current emissions and component independence.
300 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD1383VE 12.8L inline-six with SCR/DPF/DOC, DCP7310 controller, 208-600V.
300 kW Tier 4 Final mobile diesel for construction, planned outage support, and large-scale temporary power with clean emissions.
300 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD1383VE six-cylinder engine, S4L1D-E41 alternator, DCP7310 controller, 350-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD350-01
350 kW standby · Diesel · Liquid-cooled
350 kW diesel standby for large commercial, industrial, and campus facilities where value engineering and non-proprietary component access matter.
350 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1352GE 12.8L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD400-01
400 kW standby · Diesel · Liquid-cooled
400 kW diesel standby for industrial, campus, and data center facilities where value engineering and non-proprietary component access matter.
400 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1353GE 12.8L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD450-01
450 kW standby · Diesel · Liquid-cooled
450 kW diesel standby for industrial, campus, and data center facilities where value engineering and non-proprietary component access matter.
450 kW Tier 3 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1650GE 16.1L inline-six with DCP7310 controller, 208-600V output.
Tier 33-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD500-01
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for industrial, data center, and campus facilities where value engineering and non-proprietary component access matter.
500 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1641GE-B 16.1L inline-six with DCP7310 controller, 208-600V output.
Tier 23-phasecommerciallarge-commercial
Caterpillar
Cat C15
500 kW diesel with CAT C15 ACERT inline-6. Best resale value in class. ~200 US dealers with deep parts inventory.
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for hospitals, data centers, and large commercial with CAT fleet standardization.
500 kW diesel standby generator with Cat C15 ACERT engine. Large commercial standby for hospitals, high-rises, and municipal infrastructure.
80 kW diesel standby for mid-size commercial, assisted living, and schools with CAT fleet.
80 kW diesel standby generator with Cat C4.4 turbocharged inline-4 engine. Reliable platform for commercial standby and prime power applications.
3-phasecommercial-standbyprime-power
Caterpillar
Cat DG200
200 kW natural gas with CAT DG200. No diesel storage needed. EPA certified for non-emergency application.
200 kW standby · Natural Gas / LPG · Liquid-cooled
200 kW natural gas standby/DR for commercial buildings, hospitals, and facilities on gas mains.
200 kW natural gas generator with 10.3L V8 engine. Emergency standby, demand response, and prime power for commercial and industrial applications.
3-phasecommercial-standbydemand-response
Caterpillar
Cat DG400
400 kW natural gas with CAT CG18 engine. EPA certified emergency and non-emergency. No diesel infrastructure needed.
400 kW standby · Natural Gas · Liquid-cooled
400 kW natural gas standby/DR for large commercial, hospitals, and campus facilities on gas mains.
400 kW natural gas generator with Cat CG18 inline-6 engine. Emergency standby, demand response, and limited time power for commercial applications.
3-phasecommercial-standbydemand-response
Caterpillar
Caterpillar 3406
Diesel generator set built on the Cat 3406C engine, rated 275 to 400 ekW.
350 kW standby · Diesel · Liquid-cooled
Diesel standby for industrial plants, water treatment, and large commercial with fleet standardization.
The Caterpillar 3406C is a 275-400 kW diesel generator built on the 14.64L inline-6. Legacy platform with broad parts availability. Specs from OEM data sheet.
3-phasecommercial-standbyindustrial
Caterpillar
Caterpillar C13
350 kW diesel with CAT C13 ACERT inline-6. Best resale. ~200 US dealers.
350 kW standby · Diesel · Liquid-cooled
350 kW diesel standby for hospitals, large commercial, and industrial with CAT fleet standardization.
The Caterpillar C13 ACERT is a 350 kW standby diesel generator with EPA Tier 3 certification. 12.5L inline-6 with MEUI injection. Fuel consumption 24.9 gal/hr at full load. Complete specs and service reference.
Tier 33-phasecommercial-standbyhospital-medium
Caterpillar
Caterpillar C7
200 kW diesel with CAT C7 ACERT inline-6. Best resale value in class. ~200 US dealers. Compact footprint.
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for retail, telecom, and small commercial with CAT fleet standardization.
The Caterpillar C7.1 ACERT is a 200 kW standby diesel generator with EPA Tier 3 certification. 7.01L inline-6 with MEUI fuel injection. Compact standby power for small commercial and retail applications.
Tier 33-phasecommercial-standbyretail
Caterpillar
Caterpillar C9
250 kW diesel with CAT C9 ACERT inline-6. Best resale. ~200 US dealers.
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for mid-size commercial, schools, and light-industrial with CAT fleet.
The Caterpillar C9 ACERT is a 250 kW standby diesel generator with EPA Tier 3 emissions certification. 8.8L inline-6 with MEUI fuel injection. Ideal for retail, telecom, and light-industrial standby applications.
Tier 33-phasecommercial-standbyretail
Caterpillar
Caterpillar G3406
300 kW natural gas with CAT G3406 inline-6. No diesel storage needed. Legacy platform with deep parts availability.
300 kW standby · Natural Gas · Liquid-cooled
300 kW natural gas standby for hospitals, commercial campuses, and facilities on gas mains.
The Caterpillar G3406 is a natural gas standby generator built on the 14.6L G3406 TA inline-6 spark-ignited engine. No diesel fuel storage required. Legacy platform for hospitals, campuses, and commercial facilities.
100 kW diesel from Cummins' fully integrated QSB5 series. Accepts full rated load in a single step per NFPA 110 for Level 1 systems.
100 kW standby · Diesel · Liquid-cooled
100 kW diesel standby for office complexes, hotels, and commercial buildings requiring fast load pickup.
100 kW standby / 90 kW prime EPA Tier 3 diesel generator set at 60 Hz with the Cummins QSB5-G13 engine. Accepts full rated load in a single step per NFPA 110 for Level 1 systems; available listed to UL 2200.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C100 N6
100 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. No diesel logistics.
100 kW standby · Natural Gas / LPG · Liquid-cooled
100 kW natural gas standby for hotels, office campuses, and healthcare clinics with gas service.
100 kW natural gas standby generator with QSJ5.9G-G3 engine. 100 kW / 125 kVA standby, PowerCommand controls, AmpSentry protection, UL 2200, EPA certified. Dry weight 2812 lbs.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C110 D6
112 kW diesel on the Cummins 6BT5.9-G6 platform. Reliable commercial standby power with full Cummins vertical integration.
112 kW standby · Diesel · Liquid-cooled
112 kW diesel standby for commercial buildings and light-industrial facilities requiring mid-range emergency power between the C100 and C125.
112 kW diesel standby generator with Cummins 6BT5.9-G6 engine and PowerCommand control. Liquid-cooled, for commercial standby applications.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C125 D6
125 kW diesel with Cummins QSB5-G6 engine. Accepts full rated load in a single step per NFPA 110 Level 1.
125 kW standby · Diesel · Liquid-cooled
125 kW diesel standby for hotels, office complexes, and commercial buildings, powered by a 4-cylinder QSB5-G6 engine.
125 kW EPA Tier 3 diesel standby generator with Cummins QSB5-G6 engine and PowerCommand 1.1 control. Available UL 2200 listed; accepts full rated load in a single step per NFPA 110 Level 1.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C125 N6
125 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. Single-source warranty.
125 kW standby · Natural Gas · Liquid-cooled
125 kW natural gas standby for mid-size commercial, schools, and healthcare facilities on gas mains.
125 kW natural gas standby generator with QSJ8.9G engine. 125 kW standby, PowerCommand 2.3 controls, UL 2200, IBC Seismic, NFPA 110 capable. Quiet Connect RS125 series, weight 3915 lbs.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C150 D6
150 kW standby diesel generator set with the Cummins QSB7-G5 engine and EPA Tier 3 emissions certification.
150 kW standby · Diesel · Liquid-cooled
150 kW diesel standby for hotels, warehouses, and mid-size commercial buildings.
150 kW standby, 135 kW prime 60 Hz diesel generator set with the Cummins QSB7-G5 engine, EPA Tier 3 emissions certification and PC 1.1 as the standard controller.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C150 N6
150 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. No diesel permitting needed.
150 kW standby · Natural Gas / LPG · Liquid-cooled
150 kW natural gas standby for hotels, large retail, and commercial campuses with gas service.
150 kW natural gas/propane standby generator with Cummins QSJ8.9G 8.9L turbocharged inline-6 engine. PowerCommand control, UL 2200 listed, NFPA 110 Level 1 capable. Wet weight 1,776 kg (3,915 lbs).
175 kW standby diesel with the Cummins QSB7-G5 in-line 6-cylinder engine, EPA Tier 3, with PC 1.1 as the standard controller.
175 kW standby · Diesel · Liquid-cooled
175 kW diesel standby for hotels, office complexes, and mid-size commercial buildings requiring substantial emergency power capacity.
175 kW EPA Tier 3 diesel standby generator with the Cummins QSB7-G5 in-line 6-cylinder engine and PC 1.1 as the standard controller. A sound enclosure is offered.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C175 N6
175 kW natural gas standby with a Cummins GTA 8.3 engine and PowerCommand 1.1 control. No diesel fuel storage infrastructure.
175 kW standby · Natural Gas · Liquid-cooled
175 kW natural gas standby for schools, mid-size hotels, and commercial campuses on gas mains.
175 kW natural gas standby generator with GTA 8.3G engine. 175 kW / 219 kVA standby, PowerCommand 1.1 controls, 2202 CFH full-load, dimensions 115 x 40 x 59 in. ISO 9001:2015 manufactured.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C20 D6
20 kW diesel standby with a PC 1.1 standard controller and an available sound enclosure.
20 kW standby · Diesel · Liquid-cooled
20 kW diesel standby for small offices, retail locations, and light commercial buildings requiring backup power.
20 kW EPA Tier 4 Interim diesel standby generator with V2203M engine and PC 1.1 standard controller. Sound enclosure available, for small commercial and residential standby applications.
200 kW standby diesel generator set with a Cummins QSB7-G5 engine. PC 1.1 controller standard.
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for hospitals, data centers, and large commercial facilities.
200 kW standby (180 kW prime) 60 Hz diesel generator set with the Cummins QSB7-G5 engine, EPA Tier 3 emissions certification and the PC 1.1 standard controller.
Tier 33-phasecommercial-standbyindustrial
Cummins
Cummins C200 N6
200 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. Power Command controller.
200 kW standby · Natural Gas / LPG · Liquid-cooled
200 kW natural gas standby for large commercial, healthcare, and office towers on gas mains.
200 kW natural gas/propane commercial standby generator. Cummins' flagship gaseous unit with QSJ8.9G engine and PowerCommand 2.3 controller.
25 kW standby diesel generator set with a Cummins 4BT3.3-G5 engine, PC 1.1 control and an optional sound enclosure.
25 kW standby · Diesel · Liquid-cooled
25 kW diesel standby for small offices, retail spaces, and light commercial buildings requiring reliable backup power.
25 kW standby, 22.7 kW prime EPA Tier 3 diesel generator set at 60 Hz with a Cummins 4BT3.3-G5 engine, PC 1.1 control and an optional sound enclosure, for small commercial standby applications.
Tier 33-phasecommercial-standbysmall-office
Cummins
Cummins C250 N6
250 kW natural gas generator set that accepts full rated load in a single step per NFPA 110 Type 10 (ten seconds). No diesel logistics.
250 kW standby · Natural Gas · Liquid-cooled
250 kW natural gas standby for hospitals, multi-building campuses, and data centers on gas mains.
250 kW natural gas standby generator with Cummins GTA855E 14 L engine. PowerCommand 3.3 control, UL 2200 listed, NFPA 110 Type 10 Level 1/2 capable. EPA SI NSPS stationary emergency certified.
3-phaselarge-commercialhospital-medium
Cummins
Cummins C30 N6
30 kW natural gas standby with Cummins vertical integration. Clean-burning gas eliminates diesel storage requirements.
30 kW standby · Natural Gas / LPG · Liquid-cooled
30 kW natural gas standby for small retail, branch offices, and residential applications with natural gas service.
30 kW natural gas standby generator. 30 kW / 38 kVA standby, PowerCommand controls, AmpSentry protection, UL 2200, EPA certified.
3-phasecommercial-standby
Cummins
Cummins C300 N6
300 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. Paralleling-ready controller.
300 kW standby · Natural Gas · Liquid-cooled
300 kW natural gas standby for hospitals, university campuses, and large commercial on gas mains.
300 kW natural gas standby generator with GTA 855E engine. 300 kW / 375 kVA standby, PowerCommand 3.3 controls, 4098 CFH full-load, open set dimensions 147 x 69 x 77 in. UL 2200, EPA certified.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C35 D6
35 kW standby diesel generator set with a Cummins 4BT3.3-G5 engine, PC 1.1 control and an optional sound enclosure.
35 kW standby · Diesel · Liquid-cooled
35 kW diesel standby for small retail, branch offices, and light-industrial facilities requiring reliable emergency power.
35 kW standby, 32 kW prime EPA Tier 3 diesel generator set at 60 Hz with a Cummins 4BT3.3-G5 engine, PC 1.1 control and an optional sound enclosure, for small commercial and light-industrial standby.
Tier 33-phasecommercial-standbysmall-office
Cummins
Cummins C350 D6
Diesel standby built on the Cummins QSG12-G1: 11.8 L, in-line 6-cylinder, turbocharged, with the Cummins High Pressure Common Rail fuel system.
350 kW standby · Diesel · Liquid-cooled
Diesel standby for large hospitals, industrial plants, and data centers with critical loads.
Diesel standby generator with the Cummins QSG12-G1 in-line 6-cylinder engine and High Pressure Common Rail (HPCR) fuel system, for large commercial and industrial standby applications.
3-phasecommercial-standbylarge-commercial
Cummins
Cummins C40 D6
40 kW diesel with the Cummins 4BT3.3-G5 engine. PC 1.1 controller standard; sound enclosure available.
40 kW standby · Diesel · Liquid-cooled
40 kW diesel standby for small commercial buildings, restaurants, and light-industrial facilities needing mid-range backup power.
40 kW standby (36 kW prime) 60 Hz diesel generator set with the Cummins 4BT3.3-G5 engine, EPA Tier 3 emissions certification and the PC 1.1 standard controller, for small commercial and light-industrial standby.
Tier 33-phasecommercial-standbysmall-office
Cummins
Cummins C400 N6
400 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. Paralleling for multi-MW gas.
400 kW standby · Natural Gas · Liquid-cooled
400 kW natural gas standby for major hospitals, large campuses, and Tier II data centers on gas.
400 kW natural gas standby generator with Cummins GTA28E 28L inline-6 engine. PowerCommand 3.3 control, UL 2200 listed, EPA SI NSPS certified, NFPA 110 Type 10 Level 1/2 capable. Dimensions 4216 x 2083 x 2486 mm.
50 kW natural gas standby with Cummins vertical integration. Clean-burning gas eliminates diesel storage requirements.
50 kW standby · Natural Gas / LPG · Liquid-cooled
50 kW natural gas standby for small commercial buildings, retail stores, and light industrial facilities with natural gas service.
50 kW natural gas standby generator. 50 kW / 63 kVA standby, PowerCommand controls, AmpSentry protection, UL 2200, EPA certified.
3-phasecommercial-standby
Cummins
Cummins C500 N6
500 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. No diesel infrastructure needed.
500 kW standby · Natural Gas · Liquid-cooled
500 kW natural gas standby for data centers, large hospitals, and campus microgrids on gas mains.
500 kW natural gas standby generator with GTA 28E V12 engine. 500 kW / 625 kVA standby, PowerCommand 3.3 controls, 6994 CFH full-load, open set dimensions 166 x 82 x 98 in. UL 2200, EPA certified.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C60 D6
60 kW standby diesel with the Cummins 4BT3.3-G7 engine and PC 1.1 control; a sound enclosure is available.
60 kW standby · Diesel · Liquid-cooled
60 kW diesel standby for mid-size offices, retail centers, and commercial buildings requiring moderate emergency power capacity.
60 kW EPA Tier 3 diesel standby generator with Cummins 4BT3.3-G7 engine and PC 1.1 control, with a sound enclosure available, for commercial and light-industrial standby applications.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins C60 N6
60 kW natural gas with full Cummins vertical integration. QuietConnect-class sound levels. No diesel storage needed.
60 kW standby · Natural Gas / LPG · Liquid-cooled
60 kW natural gas standby for restaurants, small offices, and commercial buildings on gas mains.
80 kW standby diesel generator set that accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
80 kW standby · Diesel · Liquid-cooled
80 kW diesel standby for commercial buildings, healthcare clinics, and municipal water systems.
80 kW standby, 72 kW prime EPA Tier 3 diesel generator set at 60 Hz with a Cummins QSB5-G13 engine and a standard cooling package for running at up to 50 °C (122 °F) ambient. Aluminum sound-attenuated enclosures available.
Tier 33-phasecommercial-standbylight-industrial
Cummins
Cummins QSB7 (C200 D6)
200 kW diesel with QSB7 engine. Full Cummins vertical integration. 100% load in 10 seconds. Best cold-weather start (-40F).
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for hospitals, office complexes, and commercial buildings in any climate.
200 kW diesel commercial standby generator with Cummins QSB7 6.7L engine. The mid-range diesel workhorse for commercial and institutional facilities.
Tier 33-phasecommercialhealthcare
Cummins
Cummins QSL9
300 kW standby diesel generator set with the Cummins QSL9-G7 engine.
300 kW standby · Diesel · Liquid-cooled
300 kW diesel standby for hospitals, multi-building campuses, and industrial plants.
300 kW standby / 275 kW prime diesel generator with QSL9-G7 8.8L inline-6 Bosch HPCR engine. EPA Tier 3 / EU Stage IIIA compliant, Holset HX40 wastegated turbo, 24V starting.
130 kW industrial diesel with Iveco/FPT engine. Digital controller with paralleling capability.
130 kW standby · Diesel · Liquid-cooled
130 kW diesel standby for mid-size commercial, light manufacturing, and healthcare clinics.
130 kW industrial diesel standby generator. Iveco/FPT 6.7L turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
3-phasecommercial-standbylight-industrial
Generac
Generac SD150
150 kW industrial diesel with 10,000+ dealer support network. NFPA 110 compliant.
150 kW standby · Diesel · Liquid-cooled
150 kW diesel standby for hotels, warehouses, and commercial office buildings.
150 kW industrial diesel standby generator. Iveco/FPT 6.7L turbocharged-aftercooled inline-6 with electronic injection, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
175 kW diesel standby for large retail, assisted living, and mid-size industrial facilities.
175 kW industrial diesel standby generator. Generac 6.7L turbocharged-aftercooled inline-6 with electronic injection, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
3-phasecommercial-standbylight-industrial
Generac
Generac SD200
200 kW industrial diesel with Iveco/FPT 8.7L engine. Paralleling-ready controller.
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for hospitals, data centers, and large commercial complexes.
230 kW diesel standby for medium commercial buildings, multi-tenant properties, and small hospitals.
230 kW industrial diesel standby generator. Turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
3-phasecommercial-standbyindustrial
Generac
Generac SD250
250 kW industrial diesel. Proven Iveco/FPT engine. Largest US dealer network.
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for hospitals, manufacturing plants, and high-rise buildings.
250 kW industrial diesel standby generator. Iveco/FPT 8.7L turbocharged-aftercooled inline-6 with common rail injection, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
3-phasecommercial-standbylight-industrial
Generac
Generac SD275
275 kW industrial diesel. Digital control with paralleling and load management.
275 kW standby · Diesel · Liquid-cooled
275 kW diesel standby for large commercial campuses, water treatment, and healthcare facilities.
275 kW industrial diesel standby generator. Iveco/FPT 10.3L turbocharged-aftercooled inline-6 with common rail injection, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.
50 kW natural gas/LP standby. No fuel storage permits needed.
50 kW standby · Natural Gas · Liquid-cooled
50 kW natural gas standby for grocery stores, medical offices, and chain retail with gas service.
50 kW standby natural gas generator with Generac 4.5L turbocharged spark-ignited engine. EPA certified stationary emergency. Single and three-phase configurations.
3-phasecommercial-standbyindustrial-standby
Generac
Generac SG060
60 kW natural gas/LP standby. No diesel logistics. Largest dealer network (10,000+) for fast local service.
60 kW standby · Natural Gas · Liquid-cooled
60 kW natural gas standby for mid-size commercial, medical clinics, and chain restaurants.
60 kW standby natural gas generator with Generac 4.5L turbocharged spark-ignited engine. EPA certified stationary emergency. Single and three-phase configurations.
3-phasecommercial-standbyindustrial-standby
Generac
Generac SG070
70 kW natural gas/LP industrial standby. No fuel storage required.
70 kW standby · Natural Gas · Liquid-cooled
70 kW natural gas standby for large restaurants, small hotels, and commercial buildings on gas mains.
70 kW standby natural gas generator with Generac 4.5L turbocharged spark-ignited engine. EPA certified stationary emergency and demand response. Single and three-phase.
80 kW natural gas standby for assisted living, mid-size offices, and retail distribution centers.
80 kW standby natural gas generator with Generac 9.0L V8 naturally aspirated spark-ignited engine. EPA certified stationary emergency and demand response. Single and three-phase.
3-phasecommercial-standbyindustrial-standby
Generac
Generac SG100
100 kW natural gas industrial standby. No on-site diesel storage.
100 kW standby · Natural Gas / LPG · Liquid-cooled
100 kW natural gas standby for hotels, office campuses, and healthcare clinics with gas service.
100 kW industrial gaseous standby generator. Generac's commercial natural gas/LP platform competing with Kohler KG100 and Cummins C100 N6.
80 kW prime natural gas for continuous-duty applications — remote sites, mining, agriculture, and off-grid commercial.
80 kW prime-rated natural gas / LPG generator. PSI 8.8L V8 naturally aspirated, Stamford UCI274 alternator, DSE 7420 MKII. Continuous duty. Made in USA.
3-phaseprime-powerremote-site
Gillette
Gillette SP-1500
Factory-direct. PSI 8.8L turbo V8 + DSE controller — no proprietary lock-in. 3-7 day lead times.
150 kW standby · Natural Gas / LPG · Liquid-cooled
150 kW natural gas / 130 kW LP standby for large commercial, hotels, multi-family, and schools.
150 kW natural gas / 130 kW LPG stationary standby generator. Made-in-USA commercial gaseous unit with PSI 8.8L turbocharged V8 engine, Stamford alternator, and DSE 7420 MKII controller.
3-phasecommercialhealthcare
Gillette
Gillette SP-2000P
Factory-direct. PSI 8.8L high-output turbo V8 + DSE controller — no proprietary lock-in. 3-7 day lead times.
200 kW standby · Natural Gas · Liquid-cooled
200 kW natural gas standby for commercial buildings, hotels, multi-family housing, and data centers.
200 kW natural gas stationary standby generator. Made-in-USA commercial unit with PSI 8.8L high-output turbocharged V8, Stamford alternator, and DSE 7420 MKII controller. NG only.
3-phasecommercialhotel
Gillette
Gillette SP-2500P
Factory-direct. PSI 13L I6 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
250 kW standby · Natural Gas / LPG · Liquid-cooled
250 kW natural gas / 165 kW LP standby for hotels, data centers, and large commercial facilities.
250 kW natural gas / 165 kW LPG stationary standby generator. PSI 13L inline-6 turbocharged engine, Stamford S4L1DD alternator, DSE 7420 MKII. Made in USA.
3-phasecommercialhotel
Gillette
Gillette SP-3000P
Factory-direct. PSI 13L high-output I6 + DSE controller — no proprietary lock-in. 3-7 day lead times.
300 kW standby · Natural Gas / LPG · Liquid-cooled
300 kW natural gas / 165 kW LP standby for hotels, hospitals, data centers, and large commercial sites.
300 kW natural gas / 165 kW LPG stationary standby generator. PSI 13L inline-6 high-output charge air cooled engine, Stamford S4L1D alternator, DSE 7420 MKII. Made in USA.
3-phasecommercialhotel
Gillette
Gillette SP-3500
Factory-direct. PSI 14.6L V8 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
350 kW standby · Natural Gas / LPG · Liquid-cooled
350 kW natural gas / 210 kW LP standby for hotels, data centers, hospitals, and large commercial campuses.
350 kW natural gas / 210 kW LPG stationary standby generator. PSI 14.6L V8 turbocharged engine, Stamford alternator, Deep Sea 7420 controller. Made in USA.
3-phasecommercialhotel
Gillette
Gillette SP-4000
Factory-direct. PSI 21.9L V12 engine + Deep Sea controller — no proprietary lock-in. 3-7 day lead times.
400 kW standby · Natural Gas / LPG · Liquid-cooled
400 kW natural gas / 300 kW LP standby for data centers, hospitals, hotels, and large commercial campuses.
400 kW natural gas / 300 kW LPG stationary standby generator. PSI 21.9L V12 turbocharged engine, Stamford alternator, Deep Sea Electronics controller. Made in USA.
3-phasecommercialhotel
Gillette
Gillette SP-5000
Factory-direct. PSI 21.9L V12 high-output + Deep Sea controller — no proprietary lock-in. 3-7 day lead times.
500 kW standby · Natural Gas / LPG · Liquid-cooled
500 kW natural gas / 300 kW LP standby for data centers, hospitals, and large industrial or campus microgrids.
500 kW natural gas / 300 kW LPG stationary standby generator. PSI 21.9L V12 high-output turbocharged engine, Stamford HCI534 alternator, Deep Sea Electronics controller. Made in USA.
3-phasecommercialhotel
Gillette
Gillette SP-960
Factory-direct. PSI 5.7L TCAC engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
96 kW standby · Natural Gas / LPG · Liquid-cooled
96 kW natural gas / 80 kW LP standby for mid-size commercial, schools, worship centers, and light industrial.
96 kW natural gas / 80 kW LPG stationary standby generator. Made-in-USA commercial gaseous unit with PSI engine, Stamford alternator, and DSE 7420 MKII controller.
3-phasecommercialrestaurant
Gillette
Gillette SPD-1000
Factory-direct. Perkins engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
100 kW standby · Diesel · Liquid-cooled
100 kW diesel standby for commercial buildings, telecom sites, pump stations, and light industrial facilities.
100 kW stationary diesel standby generator with Perkins 1104D-E44TAG2 engine. Made-in-USA with Stamford UCI274D alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialtelecom
Gillette
Gillette SPD-1500
Factory-direct. Perkins 7.01L I6 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
150 kW standby · Diesel · Liquid-cooled
150 kW diesel standby for hospitals, hotels, commercial buildings, and municipal infrastructure.
150 kW stationary diesel standby generator with Perkins 1106D-E70TAG4 engine. Made-in-USA with Stamford UCI274G alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialhospital
Gillette
Gillette SPD-2000
Factory-direct. Perkins 7.01L I6 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
200 kW standby · Diesel · Liquid-cooled
200 kW diesel standby for hospitals, hotels, water treatment, and mid-size commercial or municipal facilities.
200 kW stationary diesel standby generator with Perkins 1106D-E70TAG5 engine. Made-in-USA with Stamford UCID274J alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialhospital
Gillette
Gillette SPD-600
Factory-direct. Perkins engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
60 kW standby · Diesel · Liquid-cooled
60 kW diesel standby for commercial buildings, telecom sites, retail stores, and pump stations.
60 kW stationary diesel standby generator with Perkins 1104D-E44TG1 engine. Made-in-USA with Stamford UCI224F alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialtelecom
Gillette
Gillette SPJD-1000
Factory-direct. John Deere 4045 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
100 kW standby · Diesel · Liquid-cooled
100 kW diesel standby for commercial, telecom, pump stations, and municipal buyers.
100 kW stationary diesel standby generator with John Deere 4045HF285 engine. USA factory built with Stamford UCI274D alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialtelecom
Gillette
Gillette SPJD-1550
Factory-direct. John Deere 6068 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
155 kW standby · Diesel · Liquid-cooled
155 kW diesel standby for hospitals, hotels, commercial buildings, and municipal infrastructure.
155 kW stationary diesel standby generator with John Deere 6068HF285 engine. USA factory built with Stamford UCI274G alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialhospital
Gillette
Gillette SPJD-2100
Factory-direct. John Deere 6068 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
210 kW standby · Diesel · Liquid-cooled
210 kW diesel standby for hospitals, hotels, water treatment, and commercial facilities.
210 kW stationary diesel standby generator with John Deere 6068HF485 engine. USA factory built with Stamford UCID274J alternator and DSE 7420 MKII controller.
Tier 33-phasecommercialhospital
Gillette
Gillette SPJD-600
Factory-direct. John Deere engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
60 kW standby · Diesel · Liquid-cooled
60 kW diesel standby for cost-conscious commercial, telecom, and municipal buyers.
60 kW stationary diesel standby generator with John Deere engine. USA factory built unit with Deep Sea controller and Stamford alternator.
Tier 33-phasecommercialtelecom
Gillette
Gillette SPVD-2500
Factory-direct. Volvo Penta 7.7L engine + Basler controller — no proprietary lock-in. 3-7 day lead times.
250 kW standby · Diesel · Liquid-cooled
250 kW diesel standby for hospitals, hotels, data centers, and mid-size commercial or industrial facilities.
200 kW Tier 4 Final diesel for hospitals, municipal sites, construction, and prime power.
200 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD1180VE 10.8L engine. SCR aftertreatment, DEF, Basler DGC-2020 controller. Made in USA.
250 kW Tier 4 Final diesel for hospitals, municipal sites, and prime power.
250 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD1381VE 12.8L engine. SCR aftertreatment, DEF, Basler DGC-2020 controller. Made in USA.
300 kW Tier 4 Final diesel for hospitals, municipal infrastructure, and prime power.
300 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD1383VE 12.8L engine. Water-to-air aftercooled, SCR+DEF, Basler DGC-2020. Made in USA.
350 kW Tier 4 Final diesel for hospitals, data centers, municipal sites, and prime power.
350 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD1385VE 12.78L engine. Water-to-air aftercooled, SCR+DEF, Basler DGC-2020. Made in USA.
Tier 4 Final3-phasecommercialhospital
Kohler
Kohler 100REOZJF
THD below 3% at 100 kW -- the healthcare and commercial default. John Deere 4045HF285 with Decision-Maker controller.
100 kW standby · Diesel · Liquid-cooled
100 kW commercial standby for hospitals, schools, retail, and institutional facilities requiring clean power and NFPA 110 compliance.
100 kW diesel commercial standby generator. Mid-range diesel workhorse for commercial facilities, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 100REZGD
100 kW industrial gaseous -- General Motors Vortec 5.7L with PM alternator, sub-3% THD. No on-site fuel storage required.
100 kW standby · LPG · Liquid-cooled
100 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
100 kW LPG industrial standby generator. Enclosed gaseous standby for commercial and institutional applications requiring clean-burning propane fuel.
3-phasecommercialhealthcare
Kohler
Kohler 100RZGD
100 kW industrial gaseous -- General Motors Vortec 5.7L with PM alternator, sub-3% THD. No on-site fuel storage required.
100 kW standby · LPG · Liquid-cooled
100 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
100 kW LPG industrial standby generator. Open-frame gaseous standby for commercial and industrial applications on propane.
3-phasecommercialhealthcare
Kohler
Kohler 125REOZJ4
THD below 3% at 130 kW -- the healthcare and commercial default. John Deere 6068HG550 with Decision-Maker controller.
130 kW standby · Diesel · Liquid-cooled
130 kW commercial standby for hospitals, schools, retail, and institutional facilities requiring clean power and NFPA 110 compliance.
130 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.
Tier 4 Final3-phasecommercialhealthcare
Kohler
Kohler 145REOZT4
130 kW mobile diesel trailer -- Tier 4 John Deere 6068HG550. DOT-towable for large temporary power and emergency deployment.
130 kW standby · Diesel · Liquid-cooled
130 kW mobile standby for large construction projects, event power, emergency response, and planned outage bridge power.
130 kW diesel mobile trailer Tier 4 Final commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.
Tier 4 Final3-phasecommercialhealthcare
Kohler
Kohler 150REOZJ4
150 kW standby · Diesel · Liquid-cooled
150 kW diesel commercial standby generator powered by John Deere.
Tier 4 Final3-phasecommercialhealthcare
Kohler
Kohler 150REOZJF
THD below 3% at 154 kW -- the healthcare and commercial default. John Deere 6068HF285K with Decision-Maker controller.
154 kW standby · Diesel · Liquid-cooled
154 kW commercial standby for hospitals, schools, retail, and institutional facilities requiring clean power and NFPA 110 compliance.
154 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 150REZGC
150 kW industrial gaseous -- PSI 8.8L Industrial with PM alternator, sub-3% THD. No on-site fuel storage required.
150 kW standby · LPG · Liquid-cooled
150 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
150 kW LPG industrial standby generator. Enclosed gaseous standby with PSI engine for mid-range commercial and institutional applications.
3-phasecommercialhealthcare
Kohler
Kohler 150RZGC
150 kW industrial gaseous -- PSI 8.8L Industrial with PM alternator, sub-3% THD. No on-site fuel storage required.
150 kW standby · LPG · Liquid-cooled
150 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
135 kW LPG industrial standby generator. Open-frame gaseous standby with PSI engine for commercial and industrial facilities.
3-phasecommercialhealthcare
Kohler
Kohler 175REOZT4
150 kW standby · Diesel · Liquid-cooled
150 kW diesel mobile trailer Tier 4 Final commercial standby generator powered by John Deere.
Tier 4 Final3-phasecommercialhealthcare
Kohler
Kohler 180REOZJG
THD below 3% at 180 kW -- the healthcare and commercial default. John Deere 6068HFG82E with Decision-Maker controller.
180 kW standby · Diesel · Liquid-cooled
180 kW commercial standby for hospitals, schools, retail, and institutional facilities requiring clean power and NFPA 110 compliance.
180 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 180REZXB
190 kW industrial gaseous -- Doosan D111TIC with PM alternator, sub-3% THD. No on-site fuel storage required.
190 kW standby · LPG · Liquid-cooled
190 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
190 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine for commercial, healthcare, and institutional applications.
3-phasecommercialhealthcare
Kohler
Kohler 180RZXB
190 kW industrial gaseous -- Doosan D111TIC with PM alternator, sub-3% THD. No on-site fuel storage required.
190 kW standby · LPG · Liquid-cooled
190 kW commercial standby on NG/LP for retail, offices, and light commercial preferring gaseous fuel over diesel.
170 kW LPG industrial standby generator. Open-frame gaseous standby with Doosan engine for commercial and industrial facilities.
3-phasecommercialhealthcare
Kohler
Kohler 200REOZJF
200 kW standby · Diesel · Liquid-cooled
200 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
200 kW diesel commercial standby generator. Large commercial diesel for hospitals, data centers, and institutional facilities.
Tier 33-phasehospitaldata-center
Kohler
Kohler 200REZXB
200 kW industrial gaseous -- Doosan D111TIC with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
200 kW standby · LPG · Liquid-cooled
200 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
200 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine for commercial, healthcare, and institutional applications.
3-phasecommercialhealthcare
Kohler
Kohler 200RZXB
200 kW industrial gaseous -- Doosan D111TIC with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
200 kW standby · LPG · Liquid-cooled
200 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
175 kW LPG industrial standby generator. Open-frame gaseous standby with Doosan engine for commercial and industrial facilities.
3-phasecommercialhealthcare
Kohler
Kohler 230REOZJE
230 kW diesel standby with sub-3% THD -- John Deere 6090HF484C. Healthcare and data center default in this power class.
230 kW standby · Diesel · Liquid-cooled
230 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
230 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 250REOZJE
255 kW diesel standby with sub-3% THD -- John Deere 6090HF484B. Healthcare and data center default in this power class.
255 kW standby · Diesel · Liquid-cooled
255 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
255 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 250REZXB
260 kW industrial gaseous -- Doosan D146L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
260 kW standby · LPG · Liquid-cooled
260 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
260 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine for large commercial and institutional applications.
3-phasecommercialhealthcare
Kohler
Kohler 250RZXB
260 kW industrial gaseous -- Doosan D146L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
260 kW standby · LPG · Liquid-cooled
260 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
224 kW LPG industrial standby generator. Open-frame gaseous standby with Doosan engine for commercial and industrial facilities.
3-phasecommercialhealthcare
Kohler
Kohler 275REOZJE
280 kW diesel standby with sub-3% THD -- John Deere 6090HF484A. Healthcare and data center default in this power class.
280 kW standby · Diesel · Liquid-cooled
280 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
280 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 300REOZJ
300 kW diesel standby with sub-3% THD -- John Deere 6090HFG86. Healthcare and data center default in this power class.
300 kW standby · Diesel · Liquid-cooled
300 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
300 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 300REZXC
300 kW standby · Natural Gas · Liquid-cooled
300 kW natural gas industrial standby generator with a Doosan engine.
3-phasecommercialhealthcare
Kohler
Kohler 300REZXC (300 kW Gas)
300 kW industrial gaseous -- Doosan D146L with PM alternator.
300 kW standby · Natural Gas · Liquid-cooled
300 kW commercial standby on NG for mid-to-large commercial, multi-tenant buildings, and institutional applications.
300 kW gaseous-fueled commercial standby generator. Note: the 300 kW Kohler gas genset is sold as the 300REZXC, not as 'KG300'.
3-phaselarge-commercialhospital
Kohler
Kohler 300REZXD
300 kW industrial gaseous -- PSI/Doosan D183L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
300 kW standby · LPG · Liquid-cooled
300 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
300 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 300RZXD
300 kW industrial gaseous -- PSI/Doosan D183L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
300 kW standby · LPG · Liquid-cooled
300 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
264 kW LPG industrial standby generator. Open-frame gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 350REOZJ
350 kW diesel standby with sub-3% THD -- John Deere 6135HF485T. Healthcare and data center default in this power class.
350 kW standby · Diesel · Liquid-cooled
350 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
350 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 350REOZJB
360 kW diesel standby with sub-3% THD -- John Deere 6135HFG84B. Healthcare and data center default in this power class.
360 kW standby · Diesel · Liquid-cooled
360 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
360 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 350REOZJC
350 kW standby · Diesel · Liquid-cooled
350 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
350 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 350REOZJD
360 kW diesel standby with sub-3% THD -- John Deere 6135HFG84B. Healthcare and data center default in this power class.
360 kW standby · Diesel · Liquid-cooled
360 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
360 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 350REZXB
355 kW industrial gaseous -- Doosan D183TIC with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
355 kW standby · LPG · Liquid-cooled
355 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
355 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 350REZXD
355 kW industrial gaseous -- PSI/Doosan D183L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
355 kW standby · LPG · Liquid-cooled
355 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
355 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 350RZXD
355 kW industrial gaseous -- PSI/Doosan D183L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.
355 kW standby · LPG · Liquid-cooled
355 kW commercial standby on NG/LP for mid-to-large commercial, multi-tenant buildings, and institutional applications.
290 kW LPG industrial standby generator. Open-frame gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 400REOZJ
400 kW diesel standby with sub-3% THD -- John Deere 6135HF485S. Healthcare and data center default in this power class.
400 kW standby · Diesel · Liquid-cooled
400 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
400 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 400REOZJC
400 kW diesel standby with sub-3% THD -- John Deere 6135HF485S. Healthcare and data center default in this power class.
400 kW standby · Diesel · Liquid-cooled
400 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
400 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 400REOZJD
410 kW diesel standby with sub-3% THD -- John Deere 6135HFG84A. Healthcare and data center default in this power class.
410 kW standby · Diesel · Liquid-cooled
410 kW commercial standby for hospitals, data centers, government, and mid-size facilities requiring NFPA 110 Level 1.
410 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.
Tier 33-phasecommercialhealthcare
Kohler
Kohler 400REZXB (400 kW Gas)
400 kW industrial gaseous -- Doosan D219TIC with PM alternator.
400 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
400 kW gaseous-fueled commercial standby generator. Kohler/Rehlko 400REZXB. Note: the 400 kW Kohler gas genset is sold as the 400REZXB, not as 'KG400'.
3-phaselarge-commercialhospital
Kohler
Kohler 400REZXD
400 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
400 kW standby · LPG · Liquid-cooled
400 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
400 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 400RZXD
400 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
400 kW standby · LPG · Liquid-cooled
400 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
304 kW LPG industrial standby generator. Open-frame gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 450REZXD
450 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
450 kW standby · LPG · Liquid-cooled
450 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
450 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 500REOZJ
500 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Decision-Maker controller for load management and paralleling.
500 kW standby · Diesel · Liquid-cooled
500 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
500 kW diesel commercial/industrial standby generator powered by John Deere. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 500REOZJC
505 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Offered with the APM402, APM603 or Decision-Maker 6000 controller; the APM603 and Decision-Maker 6000 support paralleling.
505 kW standby · Diesel · Liquid-cooled
505 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
505 kW diesel commercial standby generator. Large institutional diesel for hospitals, data centers, high-rises, and mission-critical facilities.
Tier 23-phasehospitaldata-center
Kohler
Kohler 500REZK
500 kW industrial gaseous -- Siemens SGE-24SL with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
500 kW standby · Natural Gas · Liquid-cooled
500 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
490-500 kW natural gas industrial standby generator with Siemens engine and Brushless Permanent-Magnet Pilot Exciter alternator. Large commercial and industrial backup power.
3-phasecommercialhealthcare
Kohler
Kohler 500REZXD
500 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
500 kW standby · LPG · Liquid-cooled
500 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
500 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler KG100
100 kW industrial gaseous -- Kohler KG6208THD turbo V8, sub-3% THD, rare-earth PM alternator. No fuel storage or SPCC required.
100 kW commercial standby on NG/LP for mid-size commercial, multi-family, and light industrial with reliable gas supply.
100 kW gaseous-fueled commercial standby generator. Upper-mid-range industrial gaseous unit for larger commercial facilities on natural gas or propane.
3-phasemedium-commerciallarge-retail
Kohler
Kohler KG125
125 kW industrial gaseous -- Kohler KG6208THD turbo V8 with PM alternator. No fuel storage, lower emissions, sub-3% THD.
45 kW commercial standby on NG/LP for retail, offices, and light commercial where diesel storage is impractical or prohibited.
45 kW gaseous-fueled commercial standby generator with Brushless Rare-Earth Permanent-Magnet alternator. Industrial gaseous unit for commercial backup on natural gas or propane.
3-phasecommercialhealthcare
Kohler
Kohler KG50
53 kW gaseous standby -- Kohler KG6208 NA V8 at 1800 RPM with rare-earth PM alternator.
53 kW gaseous-fueled commercial standby generator with Brushless Rare-Earth Permanent-Magnet alternator. Industrial gaseous unit for commercial backup on natural gas or propane.
3-phasecommercialhealthcare
Kohler
Kohler KG60
60 kW gaseous standby -- no fuel storage, no SPCC plan. Kohler KG6208 NA V8 at 1800 RPM with rare-earth PM alternator.
WhisperWatt 150 kVA - John Deere 6068HFG05 6.8L, 66 dBA at 23 ft, 319-gal tank.
132 kW standby · Diesel · Liquid-cooled
Portable power at 120 kW prime for large construction, events and commercial backup.
150 kVA (120 kW prime) portable diesel generator. John Deere-powered WhisperWatt Super-Silent for major construction, large events, and emergency commercial power.
WhisperWatt 20 kW single-phase — Isuzu diesel at 1800 RPM, 65 dBA at 23 ft, 120/240V output, 41.7-gal tank. Same 20 kW as the DCA-25 but for single-phase-only loads.
22 kW standby · Diesel · Liquid-cooled
Full residential or light commercial at 20 kW prime. For sites that need the power of a DCA-25 but only require single-phase 120/240V output.
20 kW prime (22 kW standby) portable diesel generator. Isuzu-powered WhisperWatt single-phase at 65 dBA — same power as the DCA-25, single-phase only.
WhisperWatt 70 kVA - 65 dBA at 23 ft. Isuzu BR-4JJ1X 3.0L, DEF/SCR Tier 4 Final, 103-gal tank, single- and three-phase output.
62 kW standby · Diesel · Liquid-cooled
Commercial temporary power at 56 kW prime. Diesel at 4.4 gph and a 103-gal tank.
70 kVA (56 kW prime) portable diesel generator. Quiet WhisperWatt Super-Silent for large construction sites, commercial events, and emergency temporary power.
Tier 4 Final3-phaseconstruction-largerental-fleet
MTU
MTU 10V0068 GS100
100 kW NG/LP standby on MTU's own 6.8L V10. Dual-fuel capable, compact under 87 in, 3-way catalyst, no diesel storage needed.
100 kW standby · Natural Gas / LPG · Liquid-cooled
Commercial dual-fuel standby at 100 kW. 1,100 CFH natural gas, same 100 kW on LP, compact V10 footprint.
100 kW natural gas standby generator with MTU 6.8LT V10 engine, 6.8 L turbocharged 10-cylinder V, dual-fuel capable (NG/LP), 1800 rpm. 3-way catalyst, EPA compliant.