The Thomson TS880 is Thomson Power Systems' mission-critical automatic transfer switch, covering 800A to 4000A with insulated-case power switching devices. Available in both 3-cycle and 30-cycle withstand configurations, it serves data centers, hospitals, and facilities where power continuity and selective coordination are non-negotiable.
The TS880 uses the TSC 900 controller as standard — a 7-inch color touchscreen with front-panel programming, comprehensive event logging, and Modbus communication. All configurations (open, closed, soft-load, bypass-isolation, service entrance, dual source) are available across the full 800-4000A range. The 30-cycle design shares its platform with Thomson's UL 1558 low-voltage power circuit breaker switchgear.
The TS880 bypass-isolation uses draw-out transfer power switching devices with key interlock mechanisms, mounted in separate barriered compartments from the ATS. The procedure:
Transfer load to the preferred source via the bypass handle
Isolate the ATS from both sources using the key interlock mechanism
Draw out the transfer switching devices for inspection or replacement
Service contacts, mechanisms, and controller with the load running on the bypassed source
Return draw-out switches, release interlocks, and return to automatic operation
The break-before-make bypass design prevents utility and generator paralleling under any circumstance. For units with closed-transition capability, the bypass can be operated in make-before-break sequence at the operator's direction.
The TS880 CTTS uses electrically interlocked insulated-case power switching units with the TSC 900 controller's built-in sync check relay. The controller monitors voltage differential and slip frequency between sources. When both are within threshold, it initiates a closed transition lasting less than 100ms. If the paralleling timer exceeds its limit, extended paralleling protection opens the other source within 500ms.
Soft-load transition is available as an additional ordering option for process loads requiring gradual transfer ramping.
We service Thomson TS880 units in Bay Area data centers and healthcare facilities. The insulated-case switching mechanism is extremely robust at these current levels — contact life far exceeds contactor-based alternatives in this amperage class. Annual thermographic scanning under load is essential for all frames, not just the larger ones — at 800A+, any loose busbar connection generates significant heat.
The 4000A bypass-isolation units are physically massive — at 92" x 96" x 90" and up to 7,500 lbs (4-pole), they require rigging equipment and careful access planning. We've seen installation delays on retrofit projects where the freight elevator couldn't accommodate the weight or dimensions. Specify access requirements during design to avoid costly field surprises.
The TSC 900 touchscreen controller is a significant upgrade from the TSC 7320 used on the TS870. The 7-inch color display makes programming and troubleshooting faster during service calls, and the event logging with time/date stamps provides valuable forensic data when investigating transfer events.
Frequently Asked Questions
What amperage range does the Thomson TS880 cover?
The TS880 covers 800A through 4000A in 3-pole and 4-pole configurations. Standard frame sizes are 800A, 1000A, 1200A, 1600A, 2000A, 2500A, 3000A, 3200A, and 4000A. The voltage range is 208-600V for three-phase, 3 or 4-wire systems at 50/60 Hz.
What are the 3-cycle withstand ratings?
All frames 800-4000A share the same 3-cycle withstand: 100,000A at 240V, 100,000A at 480V, and 85,000A at 600V. With optional overcurrent trip units, interrupting ratings match these withstand values.
What are the 30-cycle withstand ratings?
The 30-cycle models provide 85,000A 3-cycle at all voltages up to 600V, plus 65,000A 30-cycle at all voltages up to 600V. For power switching devices without trip units, withstand is 65,000A at both 3-cycle and 30-cycle.
What controller does the TS880 use?
The TS880 uses the TSC 900 controller as standard, featuring a 7-inch color touchscreen with front-panel programming, 8 programmable output contacts, RS232 Modbus via the GHC (Graphical Human Controller), optional Ethernet Modbus TCP, USB ports, and comprehensive event logging. The TSC 900 includes built-in sync check relay for closed-transition applications.
Does the TS880 offer bypass-isolation?
Yes. The bypass-isolation configuration uses draw-out transfer power switching devices with key interlock mechanisms, mounted in separate barriered compartments. All external power cabling connects in the bypass compartment. The break-before-make design prevents utility and generator paralleling under any circumstance. Bypass units with closed-transition may be operated in make-before-break sequence at the operator's direction.
What are the physical dimensions?
ATS-only (NEMA 1): 800-2000A share one cabinet at 91.5 x 36 x 42 inches (1,500 lbs); 2500A is 91.5 x 36 x 60 inches (1,800 lbs); 3000/3200A is 91.5 x 36 x 60 inches (2,000 lbs); 4000A is 91.5 x 48 x 72 inches (3,000 lbs). Bypass-isolation units are significantly larger — the 4000A bypass unit measures 92 x 96 x 90 inches and weighs 6,500-7,500 lbs depending on pole count.
What configurations are available beyond standard ATS?
Service entrance (SE) with integrated overcurrent protection. Bypass-isolation with draw-out switches. Closed transition (momentary, <100ms). Soft-load transition. Dual utility control (DU). Dual standby generator (DSG slave ATS). Dual prime generator (DPG). CSA Type B with integrated overcurrent and ground fault protection. 30-cycle versions of all configurations.
How does the TS880 compare to the ASCO 7000 Series?
Both target mission-critical applications. The TS880 starts at 800A with insulated-case switching and offers both 3-cycle and 30-cycle models. The ASCO 7000 starts at 30A with contactor switching. The TS880's 30-cycle design shares its platform with Thomson's UL 1558 switchgear, enabling seamless integration into paralleling switchgear packages. ASCO has broader distributor availability; Thomson typically offers more competitive pricing on large-frame mission-critical units.
What seismic certifications does the TS880 have?
The TS880 is seismic certified per IBC 2012 Section 13, Occupancy Category IV, ASCE7-05 Region 3 (minimum Ss=200%), and OSHPD certified. The OSHPD certification qualifies it for California hospital installations where healthcare-specific seismic requirements apply.
Service Specifications
Service
Frequency
Notes
Exercise under load
Monthly (NFPA 110)
30+ minutes runtime with full load transfer; verify both open and closed transition if equipped
Connection torque inspection
Annually
Critical on all frames; thermal cycling loosens insulated-case switch connections
Contact inspection
Every 3 years or 500 operations
Mission-critical units warrant more frequent inspection; check silver alloy contacts for pitting
Bypass-isolation mechanism
Annually
Exercise bypass through full travel; verify key interlocks and draw-out mechanism engage properly
Controller firmware
As released
TSC 900 updates via USB or Ethernet; backup configuration via touchscreen before updating
Thermographic scan
Annually
IR scan of all bus connections and insulated-case switch contacts under load; essential for all frame sizes
Key Terms
Insulated-case switch
Power switching device with molded insulation surrounding the contacts and mechanism. Used in the TS880 for high withstand ratings. The 30-cycle design shares the same platform as Thomson's UL 1558 low-voltage power circuit breaker switchgear.
Bypass-isolation
Configuration with draw-out transfer switches and key interlocks in separate barriered compartments. Allows maintenance personnel to isolate and bypass the ATS without interrupting power. Break-before-make design prevents source paralleling.
3-cycle vs 30-cycle withstand
3-cycle (50ms at 60Hz) is standard. 30-cycle (500ms) provides additional margin for selective coordination in mission-critical facilities. The 30-cycle design uses insulated-case power switching devices rated 800-4000A.
TSC 900 controller
Thomson's standard controller for the TS880 with 7-inch color touchscreen, front-panel programming with password security, 8 programmable output contacts, RS232 Modbus via GHC, optional Ethernet Modbus TCP, USB ports, and event logging with time/date stamping.
Soft-load transition
A controlled ramp transfer that gradually shifts load between sources, minimizing transient voltage and frequency disturbances. Available as an ordering option on the TS880.
CSA Type B
TS880 option integrating overcurrent protection and ground fault protection within the ATS, eliminating the need for separate upstream protective devices.
Found in these gensets
Generator models that ship with or are commonly paired with the Thomson TS880 Automatic Transfer Switch.
Blue Star Power Systems
Blue Star MD1000-01
Open Basler controller + Mitsubishi V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component independence matter.
1000 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12H-Y2PTAW-1 37.1L V12 engine, Stamford S6L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1250-01
Open Basler controller + Mitsubishi V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and open-architecture components matter.
1250 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12R-Y2PTAW-1 49.0L V12 engine, Stamford S6L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1600-01
Open Basler controller + Mitsubishi V16 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and non-proprietary components matter.
1600 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S16R-Y2PTAW-1 65.4L V16 engine, Stamford S7L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD2000-01
Open Basler controller + Mitsubishi V16 engine + Stamford alternator — no proprietary lock-in. 2 MW class without OEM dealer dependency.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for data centers, hospitals, and utility-scale applications where component independence and value engineering matter.
2000 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S16R-Y2PTAW2-1 65.4L V16 engine, Stamford S7L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD800-01
Open Basler controller + Mitsubishi V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for industrial plants, campus power, and data centers where value engineering and non-proprietary component access matter.
800 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12A2-Y2PTAW-2 33.9L V12 engine, Stamford S6L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star NG1050-01
Open Basler controller + PSI V16 engine + Stamford alternator — no proprietary lock-in. 1 MW gas class without OEM dealer dependency.
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
1050 kW natural gas standby for data centers, campus power, and utility-scale gas applications where component independence matters.
1050 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.
Open Basler controller + PSI V16 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
900 kW prime natural gas for continuous-duty data center, CHP, and utility-scale applications needing 24/7 gas-fueled power.
900 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.
Open Basler controller + PSI high-output V16 engine + Stamford alternator — no proprietary lock-in. 1.25 MW gas class without OEM dealer dependency.
1.3 MW standby · Natural Gas · Liquid-cooled
1250 kW natural-gas-only standby for data centers and utility-scale facilities where gas-fueled backup and component independence matter.
1250 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 53LHO high-output V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V. LP not available.
Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.
500 kW standby · Natural Gas / LPG · Liquid-cooled
500 kW natural gas standby for large commercial, campus, and data center facilities where gas-fueled backup and component independence matter.
500 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI V12 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
500 kW standby · Natural Gas / LPG · Liquid-cooled
450 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power.
450 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI high-output V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech.
500 kW standby · Natural Gas · Liquid-cooled
500 kW natural-gas-only standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
500 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 21.9LHO high-output V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V. LP not available.
Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.
600 kW standby · Natural Gas / LPG · Liquid-cooled
600 kW natural gas standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
600 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI V12 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
600 kW standby · Natural Gas / LPG · Liquid-cooled
540 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power.
540 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.
650 kW standby · Natural Gas / LPG · Liquid-cooled
650 kW natural gas standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
650 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI V12 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
650 kW standby · Natural Gas / LPG · Liquid-cooled
550 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power.
550 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. 800 kW gas class without OEM dealer dependency.
800 kW standby · Natural Gas / LPG · Liquid-cooled
800 kW natural gas standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
800 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-4160V.
Open Basler controller + PSI V12 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
800 kW standby · Natural Gas / LPG · Liquid-cooled
660 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power at scale.
660 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-4160V.
Open Basler controller + Perkins engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for industrial, data center, and campus facilities where value engineering and non-proprietary component access matter.
500 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2506C-E15TAG3 six-cylinder engine with charge air cooling, Stamford HCI534D alternator, DSE DCP7310 controller.
Tier 23-phasecommercialindustrial
Blue Star Power Systems
Blue Star PD550-01
Open Basler controller + Perkins engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
550 kW standby · Diesel · Liquid-cooled
550 kW diesel standby for industrial, data center, and campus facilities where value engineering and open-architecture components matter.
550 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2506C-E15TAG4 six-cylinder engine with charge air cooling, Stamford HCI534E alternator, DSE DCP7310 controller.
Tier 23-phasecommercialindustrial
Blue Star Power Systems
Blue Star PD600-01
Open Basler controller + Perkins engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
600 kW standby · Diesel · Liquid-cooled
600 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component access matter.
600 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2806C-E18TAG3 six-cylinder engine with charge air cooling, Stamford HCI534E alternator, DSE DCP7310 controller.
Tier 23-phasecommercialindustrial
Blue Star Power Systems
Blue Star PD750-01
Open Basler controller + Perkins engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
750 kW standby · Diesel · Liquid-cooled
750 kW diesel standby for industrial, data center, and mission-critical facilities where value engineering and non-proprietary components matter.
750 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2806C-E18TTAG7 twin-turbocharged six-cylinder engine, Stamford S6L1D-C alternator, DSE DCP7310 controller.
Tier 23-phasecommercialindustrial
Blue Star Power Systems
Blue Star VD500-01
Open Basler controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for industrial, data center, and campus facilities where value engineering and non-proprietary component access matter.
500 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1641GE-B 16.1L inline-six with DSE DCP7310 controller, 208-600V output.
Tier 23-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD550-01
Open Basler controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
550 kW standby · Diesel · Liquid-cooled
550 kW diesel standby for industrial, data center, and campus facilities where value engineering and open-architecture components matter.
550 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1642GE-B 16.1L inline-six with DSE DCP7310 controller, 208-600V output.
Tier 23-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD550-04FT4
Open Basler controller + Volvo Penta engine + Stamford alternator — Tier 4 Final compliant, no proprietary lock-in. Serviceable by any qualified tech.
550 kW standby · Diesel · Liquid-cooled
550 kW Tier 4 Final diesel standby for industrial, data center, and campus facilities requiring current emissions and component independence.
550 kW standby / 500 kW prime Tier 4 Final diesel generator from Blue Star Power Systems. Volvo Penta TWD1682GE 16.12L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + Volvo Penta engine + Leroy-Somer alternator — trailer-mounted, no proprietary lock-in. Serviceable by any qualified tech.
550 kW standby · Diesel · Liquid-cooled
550 kW Tier 4 Final mobile diesel for industrial temporary power, planned outage support, and large-scale construction with clean emissions.
550 kW standby / 500 kW prime Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TWD1682GE six-cylinder engine, 572RSL6429 alternator, DSE DCP7310 controller, 550-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD600-01
Open Basler DGC-2020 controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech.
600 kW standby · Diesel · Liquid-cooled
600 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component access matter.
600 kW EPA Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TWD1643GE 16.1L inline-six, 208-4160V output, available with medium-voltage option.
Tier 23-phaselarge-commercialhospital
Blue Star Power Systems
Blue Star VD600-03
Open Basler controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
600 kW standby · Diesel · Liquid-cooled
600 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component access matter.
600 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TWD1644GE 16.1L inline-six with dual-stage turbo, DSE DCP7310 controller, 208-600V.
Tier 23-phasecommerciallarge-commercial
Blue Star Power Systems
Blue Star VD600-04FT4
Open Basler controller + Volvo Penta engine + Stamford alternator — Tier 4 Final compliant, no proprietary lock-in. Serviceable by any qualified tech.
600 kW standby · Diesel · Liquid-cooled
600 kW Tier 4 Final diesel standby for industrial, data center, and campus facilities requiring current emissions and component independence.
600 kW standby / 570 kW prime Tier 4 Final diesel generator from Blue Star Power Systems. Volvo Penta TWD1683GE 16.12L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, three-phase 208-600V.
Open Basler controller + Volvo Penta engine + Leroy-Somer alternator — trailer-mounted, no proprietary lock-in. Serviceable by any qualified tech.
600 kW standby · Diesel · Liquid-cooled
600 kW Tier 4 Final mobile diesel for industrial temporary power, planned outage support, and large-scale construction with clean emissions.
600 kW standby / 570 kW prime Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TWD1683GE six-cylinder engine, 572RSL6431 alternator, DSE DCP7310 controller, 550-gallon integrated fuel tank.
Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems
Blue Star VD700-01
Open Basler controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. 700 kW class without OEM dealer dependency.
700 kW standby · Diesel · Liquid-cooled
700 kW diesel standby for industrial, data center, and mission-critical facilities where value engineering and non-proprietary components matter.
700 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TWD1744GE 17.3L inline-six with Common Rail injection, DSE DCP7310 controller, 208-600V.
Tier 23-phaselarge-commercialhospital
Caterpillar
Cat 3512
1000 kW diesel with CAT 3512 V-12. Best resale value in class. ~200 US dealers with parts availability back decades.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for Tier III data centers, large hospitals, and industrial campuses with CAT fleet.
1000-1400 kVA diesel generator with Cat 3512 V-12 engine. 51.8L displacement, Woodward governor, continuous/prime/standby ratings.
3-phasecommercial-standbyindustrial
Caterpillar
Cat 3512B
1500 kW diesel with CAT 3512B V-12. Best resale -- retains 15-25% more than Cummins/MTU. Deepest parts network.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
1230-1500 kW diesel generator with Cat 3512B V-12 engine. EUI fuel system, EMCP 4.2B controller, mission-critical and standby ratings.
3-phasecommercial-standbymission-critical
Caterpillar
Cat 3516
1600 kW diesel with CAT 3516 V-16. Best resale -- retains 15-25% more than competitors. ~200 US dealer network.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW diesel standby for large data centers, hospitals, and industrial campuses with CAT fleet standardization.
1600 kW diesel generator with Cat 3516 turbocharged V-16 engine. Mission-critical platform for data centers, hospitals, and large industrial standby and prime power.
3-phasedata-centerhospital
Caterpillar
Cat 3516B
2000 kW diesel with CAT 3516B V-16. Best resale value in class. Paralleling for multi-MW. ~200 US dealers.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for Tier IV data centers, large hospitals, and campus-scale critical infrastructure.
2500 kW diesel with CAT 3516C V-16. EPA Tier 4 Final. Best resale in class. Paralleling for multi-MW arrays.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW diesel standby for hyperscale data centers, campus microgrids, and emission-regulated industrial.
2500 kW diesel standby generator with Cat 3516C V-16 engine. The largest Cat genset platform for mission-critical data centers and industrial power.
Tier 23-phasedata-centerhospital-large
Caterpillar
Cat 3516E
3000 kW diesel with CAT 3516E V-16. Best resale value in class. Paralleling for multi-MW. ~200 US dealers.
3 MW standby · Diesel · Liquid-cooled
3000 kW diesel standby for hyperscale data centers, campus microgrids, and utility peak shaving.
Up to 3000 kW diesel generator with Cat 3516E V-16 engine. 78.1L displacement, Tier 2 equivalent, ATAAC aspiration for standby and mission-critical power.
Tier 23-phasecommercial-standbymission-critical
Caterpillar
Cat C15
500 kW diesel with CAT C15 ACERT inline-6. Best resale value in class. ~200 US dealers with deep parts inventory.
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for hospitals, data centers, and large commercial with CAT fleet standardization.
500 kW diesel standby generator with Cat C15 ACERT engine. Large commercial standby for hospitals, high-rises, and municipal infrastructure.
Tier 23-phasehospitalhigh-rise
Caterpillar
Cat C175-16
3100 kW diesel with CAT C175-16 V-16. Medium-voltage capable (4160V/13.8kV). Best resale. Paralleling for multi-MW.
3.1 MW standby · Diesel · Liquid-cooled
3100 kW diesel standby for hyperscale data centers, campus microgrids, and mission-critical infrastructure.
2500-3100 kW diesel generator with Cat C175-16 SCAC V-16 engine. 84.7L displacement, Tier 2, mission-critical and standby power for data centers and large industrial facilities.
Tier 23-phasecommercial-standbymission-critical
Caterpillar
Cat C175-20
4000 kW diesel with CAT C175-20 V-20. CAT largest genset. Medium-voltage capable. Best resale in class.
4 MW standby · Diesel · Liquid-cooled
4000 kW diesel standby for hyperscale data centers, utility-scale backup, and campus microgrids.
Up to 4000 kW diesel generator with Cat C175-20 SCAC V-20 engine. 105.8L displacement, mission-critical and continuous duty power for large industrial and utility applications.
3-phasecommercial-standbymission-critical
Caterpillar
Cat C27
800 kW diesel with CAT C27 V-12. Best resale -- retains 15-25% more than competitors. Paralleling-ready.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for mission-critical data centers, large hospitals, and industrial campuses.
750 kW natural gas with CAT G3512 V-12. Continuous/prime rated. Biogas capable. Best resale in gas class.
750 kW standby · Natural Gas · Liquid-cooled
750 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and campus power.
750 kW natural gas generator with Cat G3512 turbocharged V-12 engine. Continuous and prime-rated platform for cogeneration, biogas, and distributed power.
3-phasecontinuous-powerprime-power
Caterpillar
Cat G3516H
1982 kW natural gas with CAT G3516H V-16. 43.5% electrical efficiency. Cogeneration-ready. Best resale in class.
2.0 MW standby · Natural Gas · Liquid-cooled
1982 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and utility power.
1982 kW continuous natural gas generator with Cat G3516H V-16 engine. High-efficiency combined heat and power for industrial, utility, and distributed generation.
3-phasecogenerationdistributed-generation
Caterpillar
Cat G3516H
2027 kW natural gas with CAT G3516H V-16. Medium-voltage capable. Cogeneration-ready. Best resale in class.
2.0 MW standby · Natural Gas · Liquid-cooled
2027 kW natural gas continuous/cogeneration for industrial CHP, distributed generation, and campus power.
Up to 2027 kW natural gas generator with Cat G3516H V-16 engine. Continuous duty, low-emission gas power for cogeneration, distributed generation, and industrial applications.
2022 kW natural gas with CAT G3520E V-20. 41.5% electrical efficiency. Cogeneration-ready. Best resale in class.
2.0 MW standby · Natural Gas · Liquid-cooled
2022 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and baseload power.
2022 kW continuous natural gas generator with Cat G3520E V-20 engine. High-efficiency CHP platform for industrial, utility, and distributed generation.
3-phasecogenerationdistributed-generation
Caterpillar
Cat G3520H
2519 kW natural gas with CAT G3520H V-20. Medium-voltage capable. Hydrogen-blend ready. Best resale in class.
2.5 MW standby · Natural Gas · Liquid-cooled
2519 kW natural gas continuous/cogeneration for industrial CHP, distributed generation, and campus power.
Up to 2519 kW natural gas generator with Cat G3520H V-20 engine. 97.5L displacement, continuous duty, hydrogen-blend capable for cogeneration and distributed generation.
3-phasecontinuous-dutycogeneration
Caterpillar
Caterpillar 3412
720 kW diesel with legendary CAT 3412 engine. Best resale -- retains 15-25% more than competitors. Parts back to 1995.
720 kW standby · Diesel · Liquid-cooled
720 kW diesel standby for large industrial, hospitals, and mission-critical facilities with CAT fleet standardization.
The Caterpillar 3412C is a 680-900 kVA diesel generator built on the 27.02L V12 engine. ADEM A5 governor. Fuel: 45.3 gal/hr at full load. Legacy platform for hospitals, campuses, and industrial sites.
3-phasehospital-largeindustrial
Caterpillar
Caterpillar 3512C
1500 kW diesel with CAT 3512C V-12. EPA Tier 4 Final. Best resale value in class. ~200 US dealers.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, hospitals, and emission-sensitive industrial sites.
The Caterpillar 3512C is a 1500 kW standby diesel generator. 51.8L V12 ATAAC, 14.7:1 compression, EPA Tier 2. Fuel: 104.6 gal/hr at full load. Medium-voltage outputs to 13,800V for mission-critical applications.
Tier 23-phasedata-centerhospital-large
Caterpillar
Caterpillar C18
600 kW diesel with CAT C18 ACERT inline-6. Best resale -- retains 15-25% more than Cummins/MTU. ~200 US dealers.
600 kW standby · Diesel · Liquid-cooled
600 kW diesel standby for large data centers, hospitals, and industrial plants with CAT fleet.
The Caterpillar C18 ACERT is a 600 kW standby diesel generator with EPA Tier 2 certification. 18.1L inline-6 with MEUI injection. Fuel: 42.7 gal/hr at full load. Supports 4160V medium-voltage for hospital and campus applications.
Tier 23-phasehospital-mediumcampus
Caterpillar
Caterpillar G3412
512 kW natural gas with CAT G3412 V-12. No diesel infrastructure needed. EMCP 4 controller. ~200 US dealers.
512 kW standby · Natural Gas · Liquid-cooled
512 kW natural gas standby for large hospitals, campuses, and data centers on gas mains.
The Caterpillar G3412 is a 512 kW standby natural gas generator built on the 27L V12 G3412C engine. EPA Subpart JJJJ certified. EMCP 4 controller. Dry weight 14,330 lb. Complete specs from OEM sheet.
500 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. No diesel infrastructure needed.
500 kW standby · Natural Gas · Liquid-cooled
500 kW natural gas standby for data centers, large hospitals, and campus microgrids on gas mains.
500 kW natural gas standby generator with GTA 28E V12 engine. 500 kW / 625 kVA standby, PowerCommand 3.3 controls, 6994 CFH full-load, open set dimensions 166 x 82 x 98 in. UL 2200, EPA certified.
3-phasecommercial-standbyindustrial-standby
Cummins
Cummins C750 N6
750 kW natural gas with full Cummins vertical integration. GTA50 engine platform. Paralleling for multi-MW gas backup.
750 kW standby · Natural Gas · Liquid-cooled
750 kW natural gas standby for mission-critical data centers and large campus power on gas mains.
750 kW standby natural gas generator with GTA50 engine. PowerCommand 3.3 controls, AmpSentry protection, UL 2200, NFPA 110 Type 10 load acceptance.
3-phasecommercial-standbyindustrial
Cummins
Cummins KTA38
887 kW diesel with legendary KTA38 engine. Full Cummins vertical integration. Parts availability back decades.
887 kW standby · Diesel · Liquid-cooled
887 kW diesel standby for large industrial plants, hospitals, and mission-critical infrastructure.
887 kW standby / 811 kW prime diesel generator at 50 Hz. KTA38-G5 37.8L V12 PT fuel injection. Legacy Cummins platform for industrial, hospital, campus, and mining standby applications.
3-phaseindustrialhospital-large
Cummins
Cummins KTA50
1340 kW diesel with legendary KTA50 engine. Full Cummins vertical integration. 10-15% below CAT 3512 class.
1.3 MW standby · Diesel · Liquid-cooled
1340 kW diesel standby for Tier III+ data centers, large hospitals, and heavy industrial plants.
1340 kW standby / 1200 kW prime diesel generator at 50 Hz. KTA50-GS8 50.3L V16 PT fuel injection, 2-pump 2-loop cooling. Legacy Cummins platform for data center, industrial, hospital, and mining standby applications.
3-phasedata-centerhospital-large
Cummins
Cummins QSK19
550 kW diesel with QSK19 engine. Full Cummins vertical integration. Power Command controller. 10-15% below CAT.
550 kW standby · Diesel · Liquid-cooled
550 kW diesel standby for large data centers, hospitals, and heavy industrial plants.
550 kW standby / 500 kW prime diesel generator with QSK19-G4 19L inline-6 MCRS engine. EPA Tier 2, CTT HX83 turbocharging, 24V starting. Engine dimensions 1695 x 985 x 1723 mm, dry weight 1900 kg.
Tier 23-phasehospital-mediumcampus
Cummins
Cummins QSK23
800 kW diesel with QSK23 engine. Full Cummins vertical integration. 100% load in 10 seconds. 10-15% below CAT.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for mission-critical data centers, large hospitals, and industrial campuses.
800 kW standby / 727 kW prime diesel generator with QSK23-G3 23.1L inline-6 HPI-PT engine. Non-regulated, CTT HX82 turbocharging, 24V starting. Engine dimensions 2976 x 1656 x 1964 mm, dry weight 3245 kg.
Tier 23-phasehospital-largecampus
Cummins
Cummins QSK38
1160 kW diesel with QSK38 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT.
1.2 MW standby · Diesel · Liquid-cooled
1160 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
1160 kW standby / 965 kW prime diesel generator with QSK38-G5 37.7L V12 MCRS engine. EPA Tier 2, 2P2L cooling, 24V starting. Engine dimensions 2081 x 1492 x 1860 mm, dry weight 4100 kg.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins QSK50
1500 kW diesel with QSK50 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT 3512.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier IV data centers, university campuses, and major industrial plants.
1500 kW standby / 1365 kW prime diesel generator with QSK50-G4 50.3L V16 MCRS engine. EPA Tier 2 and TA Luft compliant, 2P2L cooling, 24V starting. Engine dimensions 4674 x 2468 x 3100 mm, dry weight 7429 kg.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins QSK60
2000 kW diesel with QSK60 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT 3516.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for hyperscale data centers, large hospitals, and campus microgrids.
2000 kW diesel standby generator. The data center industry standard — V-16, 60.2L, Tier 2. Cummins' flagship for mission-critical power.
Tier 23-phasedata-centerhospital
Cummins
Cummins QSK78
2750 kW diesel with QSK78 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT 3516B.
2.8 MW standby · Diesel · Liquid-cooled
2750 kW diesel standby for hyperscale data centers, critical infrastructure, and utility peaking.
2750 kW standby / 2500 kW prime diesel generator with QSK78-G14 V18 engine. EPA Tier 4 Final, 78-liter displacement for mission-critical and data center power.
Tier 4 Final3-phasedata-centerhospital
Cummins
Cummins QSK95
3010 kW diesel with QSK95 engine -- Cummins largest. Full vertical integration. Paralleling for campus-scale power.
3.0 MW standby · Diesel · Liquid-cooled
3010 kW diesel standby for hyperscale data centers, campus microgrids, and utility peak shaving.
3010 kW standby / 2690 kW prime diesel generator with QSK95-G10 V16 engine. EPA Tier 2, quad turbo, MCRS fuel injection, ISO 8528-G3 transient capability.
Tier 23-phasedata-centerhospital
Cummins
Cummins QSX15
500 kW diesel with QSX15 engine. Full Cummins vertical integration. Power Command controller. 10-15% below CAT.
500 kW standby · Diesel · Liquid-cooled
500 kW diesel standby for major hospitals, Tier III data centers, and large industrial facilities.
500 kW standby / 450 kW prime diesel generator with QSX15-G9 engine. 24-valve DOHC, 15-liter inline-6, EPA NSPS certified for commercial and industrial power.
3-phasecommercial-standbyindustrial
Generac
Generac SD1250
1250 kW industrial diesel with Mitsubishi engine. Competitive pricing vs CAT/Cummins. Paralleling for multi-MW systems.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
Factory-direct prime-rated gas at 15-30% below major brands. PSI 31.8L V12 — Gillette's largest prime gas unit. Continuous duty, no lock-in.
540 kW standby · Natural Gas · Liquid-cooled
540 kW prime natural gas for continuous-duty industrial, mining, and large off-grid operations. Gillette's largest prime unit.
540 kW prime-rated natural gas generator. PSI 31.8L V12 turbocharged, Stamford HCI534 alternator, DSE 7420. Continuous duty, 3-phase only. Gillette's largest prime gas unit.
Factory-direct megawatt-class gas at 15-30% below major brands. PSI 52.3L V16 engine + DSE controller — no proprietary lock-in.
1.1 MW standby · Natural Gas · Liquid-cooled
1,050 kW (1 MW) natural gas standby for data centers, hospitals, industrial campuses, and utility-scale backup.
1,050 kW natural gas stationary standby generator. PSI 52.3L V16 turbocharged engine, Stamford AVK alternator, DSE 7420 MKII. Natural gas only. Made in USA.
Factory-direct at 15-30% below major brands. PSI 31.8L V12 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
650 kW standby · Natural Gas · Liquid-cooled
650 kW natural gas standby for data centers, hospitals, industrial facilities, and campus-scale emergency backup.
650 kW natural gas stationary standby generator. PSI 31.8L V12 turbocharged engine, Stamford HCI634 alternator, DSE 7420 MKII. Natural gas only. Made in USA.
Factory-direct at 15-30% below major brands. Volvo Penta 17.26L engine + Basler controller — Gillette's largest Volvo unit. No lock-in.
700 kW standby · Diesel · Liquid-cooled
700 kW diesel standby for data centers, hospitals, industrial campuses, and large-scale municipal or commercial facilities.
700 kW stationary diesel standby generator with Volvo Penta TWD1744GE 17.26L engine. Stamford S6DC311 alternator, Basler DGC-2020 controller. Gillette's largest Volvo unit.
Tier 23-phasedata-centerhospital
Gillette
Gillette T4D-6000
Factory-direct Tier 4 Final at 15-30% below major brands. Volvo Penta 16.1L engine — Gillette's largest T4F unit. EPA/CARB compliant.
600 kW standby · Diesel · Liquid-cooled
600 kW Tier 4 Final diesel for data centers, hospitals, industrial prime power, and sites in CARB jurisdictions.
600 kW standby / 570 kW prime Tier 4 Final diesel generator with Volvo Penta TWD1683GE 16.1L engine. H2O-to-air aftercooled, SCR+DEF. Gillette's largest T4F unit.
Tier 4 Final3-phasedata-centerhospital
Kohler
Kohler 1250REOZMD
1280 kW diesel standby -- Mitsubishi S12R-Y2PTAW-1, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.3 MW standby · Diesel · Liquid-cooled
1280 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1280 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 1250ROZMC
1120 kW diesel standby -- Mitsubishi S12R V12 turbo, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.1 MW standby · Diesel · Liquid-cooled
1120 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1120 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1600REOZMD
1600 kW industrial diesel -- Mitsubishi S16R-Y2PTAW-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1600 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
1560 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1560 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1750REOZMD
1780 kW industrial diesel -- Mitsubishi S16R-Y2PTAW2-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.8 MW standby · Diesel · Liquid-cooled
1780 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1780 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 2000REOZMD
2000 kW industrial diesel -- Mitsubishi S16R-Y2PTAW2-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
2 MW standby · Diesel · Liquid-cooled
2000 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
2000 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
1760 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1760 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 2500REOZDC
2500 kW industrial diesel -- Detroit Diesel/MTU 16V4000G83L with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
2500 kW diesel industrial generator powered by Detroit Diesel/MTU. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 500REOZJ
500 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Decision-Maker controller for load management and paralleling.
500 kW standby · Diesel · Liquid-cooled
500 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
500 kW diesel commercial/industrial standby generator powered by John Deere. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 500REOZJB
510 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Decision-Maker controller for load management and paralleling.
510 kW standby · Diesel · Liquid-cooled
510 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
510 kW diesel commercial/industrial standby generator powered by John Deere. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 500REOZJC
500 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Decision-Maker controller for load management and paralleling.
500 kW standby · Diesel · Liquid-cooled
500 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
500 kW diesel commercial standby generator. Large institutional diesel for hospitals, data centers, high-rises, and mission-critical facilities.
Tier 23-phasehospitaldata-center
Kohler
Kohler 500REOZVC
515 kW diesel standby -- Volvo TAD1641GE-B, sub-3% THD. Decision-Maker controller for load management and paralleling.
515 kW standby · Diesel · Liquid-cooled
515 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
515 kW diesel commercial/industrial standby generator powered by Volvo. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 500REZK
500 kW industrial gaseous -- Siemens SGE-24SL with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
500 kW standby · Natural Gas · Liquid-cooled
500 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
490-500 kW natural gas industrial standby generator with Siemens engine and Brushless Permanent-Magnet Pilot Exciter alternator. Large commercial and industrial backup power.
3-phasecommercialhealthcare
Kohler
Kohler 500REZXD
500 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.
500 kW standby · LPG · Liquid-cooled
500 kW gaseous standby for large commercial, industrial, and campus applications where NG eliminates diesel logistics and permitting.
500 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.
3-phasecommercialhealthcare
Kohler
Kohler 550REOZVB
550 kW diesel standby -- Volvo TAD1642GE-B, sub-3% THD. Decision-Maker controller for load management and paralleling.
550 kW standby · Diesel · Liquid-cooled
550 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
550 kW diesel commercial/industrial standby generator powered by Volvo. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 600REOZVB
600 kW diesel standby -- Volvo TWD1643GE, sub-3% THD. Decision-Maker controller for load management and paralleling.
600 kW standby · Diesel · Liquid-cooled
600 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
600 kW diesel commercial/industrial standby generator powered by Volvo. Suitable for hospitals, data centers, and large commercial complexes.
Tier 23-phasecommercialhealthcare
Kohler
Kohler 750REOZMD
760 kW diesel standby -- Mitsubishi S12A2-Y2PTAW-2, sub-3% THD. Decision-Maker controller for load management and paralleling.
760 kW standby · Diesel · Liquid-cooled
760 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
760 kW diesel commercial/industrial standby generator powered by Mitsubishi. Suitable for hospitals, data centers, and large commercial complexes.
1250 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1250 kW EPA Tier 4 Final diesel industrial standby generator. Dual-certified (emergency and non-emergency) for mission-critical and prime power applications.
1750 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1750 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2000
2000 kW KD Series -- Kohler KD62V12 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.
2 MW standby · Diesel · Liquid-cooled
2000 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2000 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure requiring multi-megawatt backup.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2250
2250 kW KD Series -- Kohler KD62V12 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.
2.3 MW standby · Diesel · Liquid-cooled
2250 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2250 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical facilities approaching 2 MW.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2500
2500 kW KD Series -- Kohler KD62V12 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2500 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and heavy industrial facilities requiring 2+ MW backup.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2500-4
2500 kW KD Series -- Kohler KD62V12 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2500 kW EPA Tier 4 Final diesel industrial standby generator. Dual-certified (emergency and non-emergency) for mission-critical and prime power applications.
Tier 4 Final3-phasedata-centerhealthcare
Kohler
Kohler KD2800
2800 kW KD Series -- Kohler KD83V16 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.
2.8 MW standby · Diesel · Liquid-cooled
2800 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2800 kW diesel industrial standby generator. Upper-range KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD3000
3000 kW KD Series -- Kohler KD83V16 engine, skewed stator for sub-3% THD. Purpose-built for multi-MW mission-critical paralleling.
3 MW standby · Diesel · Liquid-cooled
3000 kW industrial standby for Tier IV data centers, large hospitals, and campus microgrids. NFPA 110 Level 1, UL 2200 listed.
3000 kW diesel industrial standby generator. Upper-range KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD3250
3250 kW KD Series -- Kohler KD83V16 engine, skewed stator for sub-3% THD. Purpose-built for multi-MW mission-critical paralleling.
3.3 MW standby · Diesel · Liquid-cooled
3250 kW industrial standby for Tier IV data centers, large hospitals, and campus microgrids. NFPA 110 Level 1, UL 2200 listed.
3250 kW diesel industrial standby generator. Upper-range KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD3250-4
3250 kW KD Series -- Kohler KD83V16 engine, skewed stator for sub-3% THD. Purpose-built for multi-MW mission-critical paralleling.
3.3 MW standby · Diesel · Liquid-cooled
3250 kW industrial standby for Tier IV data centers, large hospitals, and campus microgrids. NFPA 110 Level 1, UL 2200 listed.
3250 kW EPA Tier 4 Final diesel industrial standby generator. Dual-certified (emergency and non-emergency) for mission-critical and prime power applications.
Tier 4 Final3-phasedata-centerhealthcare
Kohler
Kohler KD3500
3500 kW KD Series -- Kohler KD103V20 engine, skewed stator for sub-3% THD. Purpose-built for multi-MW mission-critical paralleling.
3.5 MW standby · Diesel · Liquid-cooled
3500 kW industrial standby for Tier IV data centers, large hospitals, and campus microgrids. NFPA 110 Level 1, UL 2200 listed.
3500 kW diesel industrial standby generator. Near-top-of-line KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD4000
4000 kW KD Series -- Kohler KD103V20 engine, skewed stator for sub-3% THD. Purpose-built for multi-MW mission-critical paralleling.
4 MW standby · Diesel · Liquid-cooled
4000 kW industrial standby for Tier IV data centers, large hospitals, and campus microgrids. NFPA 110 Level 1, UL 2200 listed.
4000 kW diesel industrial standby generator. Flagship KD Series platform — the largest single-engine generator in Kohler's industrial lineup.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD900
900 kW KD Series -- Kohler KD27V12 with sub-3% THD and PM pilot exciter. Clean power for sensitive loads.
900 kW standby · Diesel · Liquid-cooled
900 kW industrial standby for data centers, hospitals, and mission-critical facilities requiring premium power quality and NFPA 110 Level 1.
900 kW diesel industrial standby generator. Entry-level KD Series platform for data centers, healthcare, and mission-critical facilities.
Tier 23-phasedata-centerhealthcare
M
MTU
MTU 10V1600 DS500
500 kW diesel standby on MTU 10V1600 V10 — 17.5L, ADEC isochronous ±0.25%, PMG alternator with 300% short-circuit, 33 gph, 20K-hr overhaul.
500 kW standby · Diesel · Liquid-cooled
Data center and critical facility standby at 500 kW. Diesel at 33 gph, PMG for UPS compatibility, NFPA 110 single-step.
500 kW diesel standby generator with MTU 10V1600G80S 17.5L common-rail V10 engine, EPA Tier 2, 208–600V three-phase, PMG alternator, ADEC isochronous governor. 3416 x 1873 x 2032 mm.
Industrial/data center standby at 600 kW. Diesel at 40 gph, 12-cyl V platform, PMG for UPS and motor starting.
600 kW diesel standby generator with MTU 12V1600G80S 21.0L common-rail V12 engine, EPA Tier 2, 208–600V three-phase, PMG alternator, ADEC isochronous governor. 3737 x 1899 x 2137 mm.
Tier 23-phasecommercial-standbyindustrial-standby
M
MTU
MTU 12V1600 DS750
750 kW diesel standby — 12V1600 sweet spot. Same footprint as DS600/DS900, 50°C radiator, 51 gph, Leroy-Somer alternator.
750 kW standby · Diesel · Liquid-cooled
Healthcare/data center/high-rise standby at 750 kW. Diesel at 51 gph, compact for sub-MW class, SCAQMD + NFPA 110.
750 kW Tier 2 diesel standby generator. mtu 12V1600G71S engine, 22.44L V-12 with turbocharging and aftercooling, LSA 49.3 M8 alternator.
Tier 23-phasecommercial-standbyindustrial
M
MTU
MTU 12V1600 DS900
900 kW diesel standby — max output from 12V1600 platform. Same footprint as DS600/DS750, 62 gph, 996 kWm gross. Compact sub-MW.
900 kW standby · Diesel · Liquid-cooled
Large commercial/data center standby at 900 kW. Diesel at 62 gph, compact 178 in footprint, 40°C radiator rating.
900 kW Tier 2 diesel standby generator. mtu 12V1600G91S engine, 22.44L V-12 with turbocharging and aftercooling, LSA 49.3 L9 alternator.
Tier 23-phasecommercial-standbyindustrial
M
MTU
MTU 12V2000 DS800
800 kW diesel standby — MTU 2000-series V12, 23.9L. Medium-voltage 4,160V option, EUP injection, separate intercooler circuit, 59 gph.
800 kW standby · Diesel · Liquid-cooled
Industrial/hospital standby at 800 kW. Diesel at 59 gph, 4,160V medium-voltage available, 20K-hr overhaul interval.
800 kW diesel standby generator with MTU 12V2000G85TB 23.9L V12 engine, EPA Tier 2, 208–4160V including medium voltage, electronic unit pump injection, ADEC governor. 4675 x 2292 x 2341 mm, 17,379 lb.
Data center continuous power at 1,600 kW DCCP. Diesel at 111 gph, flagship 12-cyl, HVO renewable fuel compatible.
1,750 kW standby / 1,600 kW DCCP diesel generator from MTU (Rolls-Royce). 57.2L V12 engine, EPA Tier 2 + SCAQMD, 380-13,800V. Maximum continuous output from the 12-cylinder Series 4000.
Tier 23-phasedata-centerhospital-large
M
MTU
MTU 20V4000 DS2800
2,800 kW diesel standby — MTU 20V4000 95.4L V20. Medium/high-voltage to 13.8kV, ADEC ±0.25%, 20K-hr overhaul, 186 gph.
2.8 MW standby · Diesel · Liquid-cooled
Utility-scale standby at 2.8 MW. Diesel at 186 gph, 480V-13.8kV direct MV connection, 62,000 lb installation.
2800 kW diesel standby generator with MTU 20V4000G83 95.4L 20-cylinder V common-rail engine, EPA Tier 2, 380V–13.8kV including medium voltage, ADEC governor, 7626 x 3099 x 3569 mm, 62,056 lb.
Tier 23-phasecommercial-standbyindustrial-standby
M
MTU
MTU 20V4000 DS3250
3,250 kW diesel standby — top of the MTU product line. 95.4L V20 at 3,490 kWm, 480V-13.8kV, standby-only, 223 gph.
3.3 MW standby · Diesel · Liquid-cooled
Maximum single-unit standby at 3.25 MW. Diesel at 223 gph, 480V-13.8kV medium-voltage, 65,000+ lb power plant.
3250 kW diesel standby generator with MTU 20V4000G83L 95.4L 20-cylinder V common-rail engine, EPA Tier 2, 480V–13.8kV medium and high voltage, ADEC governor. 7766 x 3099 x 3569 mm, 65,369 lb.
Tier 23-phasecommercial-standbyindustrial-standby
Need service for the Thomson TS880 Automatic Transfer Switch?
Our technicians work on every major component OEM. We stock common parts and source rare ones.