Overview#
The Kohler 600REOZVB is a 600-kilowatt standby (555 kW prime) diesel generator powered by a Volvo TWD1643GE (or TWD1644GE) — a 16.12 L turbocharged charge-air-cooled inline-6 at 1800 RPM.
The unit is EPA Tier 2 certified for stationary emergency applications and is UL 2200 listed, meeting NFPA 110 Level 1 requirements when properly accessorized.
The 600REOZVB is approved for HVO/Renewable Diesel fuels.
Specifications#
| Spec | Value |
|---|---|
| Standby Power | 600 kW |
| Prime Power | 555 kW |
| Voltage (primary) | 277/480V three-phase |
| Frequency | 60 Hz |
| Engine | Volvo TWD1643GE |
| Engine type | 4-cycle turbocharged, charge air-cooled |
| Cylinders | 6 inline |
| Displacement | 16.12 L (984 cu. in.) |
| Compression ratio | 16.5:1 |
| Rated RPM | 1800 |
| Alternator | Kohler 5M4030 |
| Fuel | Diesel (#2 / HVO / RD) |
| Cooling | Liquid (radiator) |
| Emissions tier | EPA Tier 2 stationary emergency |
| Fuel consumption (100% standby load) | 42.7 gph |
| Fuel consumption (75% standby load) | 31.1 gph |
| Overall dimensions | 166.5" x 72" x 78.1" |
Service & Maintenance#
The Volvo TWD1643GE uses three cartridge oil filters and a water-cooled oil cooling system. Oil pan capacity is 42.0 L (44.4 qt), 48.1 L (50.8 qt) with filter. Jacket water capacity is 33 L (8.7 gal); radiator system total capacity is 166 L (43.9 gal).
Common Failure Modes#
Charge cooler water flow for the TWD1643GE is 150 Lpm (39.6 gpm).
The battery specification is two 925 CCA 12 V batteries with an 80 A, 24 V battery charging alternator.
Our service experience#
PowerGen provides installation, maintenance, load bank testing, and emergency service for Kohler industrial generators throughout Northern California and the Central Valley.
FAQ#
Q: What engine powers the Kohler 600REOZVB? A: The 600REOZVB uses a Volvo TWD1643GE (or TWD1644GE) — a 16.12 L, 6-cylinder turbocharged charge-air-cooled diesel at 1800 RPM, EPA Tier 2 certified for stationary emergency.
Q: What is the standby power rating of the 600REOZVB? A: 600 kW standby and 555 kW prime at 0.8 power factor per Kohler spec sheet G5-396.
Q: Does OnPoint service the Kohler 600REOZVB? A: Yes. PowerGen provides maintenance, repair, and load bank testing for Kohler REOZVB diesel generators throughout Northern California, including the 600 kW class.