Blue Star Power Systems · PSI Industrial Gaseous (500-1250 kW)

Blue Star NG650-01P

Standby: see spec sheet / 550 kW prime · Natural Gas / LPG · Liquid-cooled

550 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.

Blue Star Power Systems Blue Star NG650-01P generator — specifications and details
Standby power
See spec sheet / 550 kW prime
Voltage options
120/208V, 240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 32L · 31.8L
Alternator
HCI534F

Overview#

The Blue Star NG650-01P is a prime-rated generator, delivering 550 kWe on natural gas (350 kWe on LP). It uses a PSI 32L V12 engine. Three-phase only — no single-phase option. The NG650-01P carries a 1-year / 1,500-hour prime warranty.

Alternator configurations#

VoltagePhaseAlternatorConnection
120/208V3S6L1D-C12-lead WYE
240V3S6L1D-C12-lead DELTA
277/480V3HCI534F12-lead WYE
347/600V3HCI534F4-lead WYE

All carry 105°C prime temperature rise and ±0.5% voltage regulation.

When to spec the NG650-01P#

  • 550 kW continuous or prime duty on natural gas or LP (three-phase only)
  • Facilities where the NG650-01P's deration base (87°F / 3,000 ft) is operationally relevant

Our service experience#

The oil system is 32.2 gal and the system coolant capacity is 54.4 gal.

Engineering specifications

Physical

Length
210 in
Width
96 in
Height
103 in
Dry weight
16,175 lb

Acoustic

Sound @ 7m, full load
89 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
11 in WC

Thermal & ventilation

Heat to coolant
1,748,520 BTU/hr
Heat radiated
651,900 BTU/hr
Exhaust flow
3,629 CFM
Exhaust temp
1138 °F
Combustion air
1,125 CFM
Ventilation air
41,200 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Blue Star NG650-01P

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Blue Star NG650-01P

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

5,775,000 BTU/hr≈ 5775.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Frequently Asked Questions

What is the prime rating of the NG650-01P?
The Blue Star NG650-01P is rated 550 kWe prime on natural gas and 350 kWe prime on LP at 60 Hz / 1800 RPM, backed by a 1-year / 1,500-hour prime warranty.
What are the deration thresholds for the NG650-01P?
The NG650-01P prime uses 87°F inlet air and 3,000 ft altitude as deration start points.
Is single-phase output available on the NG650-01P?
No. The NG650-01P is three-phase only, in 208V, 240V, 480V, and 600V configurations.

Compatible equipment

More in the PSI Industrial Gaseous (500-1250 kW)

500–1250 kW natural gas and LP standby power on PSI V12 and V16 spark-ignition platforms.

Similar models

Blue Star Power Systems Blue Star NG650-01 650 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG650-01

650 kW standby · Natural Gas / LPG · Liquid-cooled

650 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.

3-phaselarge-commercialdata-center
Blue Star Power Systems Blue Star NG600-01P liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG600-01P

Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled

540 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.

3-phaselarge-commercialdata-center
Blue Star Power Systems Blue Star NG600-01 600 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG600-01

600 kW standby · Natural Gas / LPG · Liquid-cooled

600 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-600V.

3-phaselarge-commercialdata-center

Services for the Blue Star NG650-01P

Need service or parts for the Blue Star NG650-01P?

We service every major OEM and stock genuine parts for the most common models.