Caterpillar · Cat 3500 Series (Gas)

Cat G3520E

2022 kW standby · Natural Gas · Liquid-cooled

2022 kW continuous natural gas generator with Cat G3520E V-20 engine. High-efficiency CHP platform for industrial, utility, and distributed generation.

Caterpillar Cat G3520E generator — specifications and details
Standby power
2022 kW
Voltage options
400V, 4160V, 11000V
Frequency / Phase
50, 60 Hz · 3-phase
Engine
Caterpillar G3520E · 9L
cogenerationdistributed-generationManufacturingutility-peakinglandfill-gas
Configure & QuoteDownload spec sheet

Overview#

The Cat G3520E is a 2022 ekW continuous natural gas engine designed for combined heat and power (CHP), distributed generation, and industrial baseload applications. As the V-20 variant of Cat's G3500 gas engine platform, it extends the proven G3516 architecture by four additional cylinders for higher power density.

The G3520E uses ADEM3 electronic controls with integrated air-fuel ratio management, separate-circuit aftercooling (SCAC), and lean-burn combustion to achieve 500 mg/Nm3 NOx engine-out while delivering 41.5% electrical efficiency.

Engine platform#

The G3520E shares the G3500 block architecture:

  • V-20 configuration with 11.9:1 compression ratio
  • SCAC (separate circuit aftercooling) -- two-stage system with jacket water/oil cooler/first-stage aftercooler on circuit one, and second-stage aftercooler on circuit two
  • ADEM3 control system with integrated air-fuel ratio management
  • Dry exhaust manifold design
  • 2000 m altitude capability at 25C inlet air -- one of the highest in the G3500 lineup

Engine output is 2100 bkW at full load, with generator efficiency of 96.3% yielding 2022 ekW net electrical output.

Efficiency and heat recovery#

At full load (ISO 3046/1):

  • Electrical output: 2022 ekW (41.5% efficiency)
  • Jacket water heat: 655 kW recoverable
  • Lube oil heat: 124 kW recoverable
  • Stage 1 aftercooler heat: 402 kW recoverable
  • Exhaust heat to 120C: 988 kW recoverable
  • Total CHP efficiency: 86.8%

The G3520E's high thermal output -- over 2 MW recoverable heat -- makes it particularly well-suited for industrial process heating and district energy applications.

Emissions profile#

The G3520E is a lean-burn engine with controlled NOx levels:

  • NOx: 500 mg/Nm3 (corrected to 5% O2) -- held constant across all load points
  • CO: 1153 mg/Nm3 at full load
  • Formaldehyde: 250 mg/Nm3

An oxidation catalyst is typically required for CO and formaldehyde compliance in most jurisdictions. The constant NOx level across load points simplifies emissions permitting compared to engines with variable NOx profiles.

Our service experience#

The G3500 gas engine platform has extensive field history in continuous-duty applications. The G3520E's 20-cylinder configuration demands disciplined spark plug management -- with 20 plugs to maintain, a systematic replacement schedule (every 4,000 hours) is essential. SCAC water quality and temperature stability remain critical: inlet manifold temperature must be controlled within +/-5C to avoid detonation. The ADEM3 system requires Cat Electronic Technician (Cat ET) for diagnostics.

Engineering specifications

Documents & downloads

Spec sheets & manuals

Units For Sale

View all (1)
New

2020

N/A

Contact for Pricing

Texas, TX

Don't see the right unit? Request a Custom Quote →

Ready to order this model?

Configure your Cat G3520E

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Cat G3520E

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

21,231,000 BTU/hr21231.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Cat G3520E under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 2000 hours
Air filter
Every 4000 hours
Major overhaul
64,000 hours

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Spark plugsMisfiring, rough running, increased emissions4,000+minor
Prechamber / ignition systemHard starting, detonation, power loss16,000+moderate
Turbocharger bearingsOil consumption, reduced boost, high exhaust temperature32,000+moderate
SCAC (separate circuit aftercooler) foulingElevated manifold air temperature, detonation risk8,000+moderate

Frequently Asked Questions

What is the rated power of the Cat G3520E?
The G3520E produces 2022 ekW (2528 kVA) continuous power at 1500 rpm without fan, per Cat technical data sheet DM8924-02. Engine brake power is 2100 bkW at full load.
How does the G3520E compare to the G3516H?
The G3520E adds four more cylinders (V-20 vs V-16) for approximately 2% more electrical output (2022 vs 1982 ekW). The G3520E uses the older ADEM3 control system versus ADEM4 on the G3516H, and has a slightly lower compression ratio (11.9:1 vs 12.1:1). The G3520E has better altitude capability (2000 m vs 1400 m).
What is the electrical efficiency of the G3520E?
41.5% genset efficiency at full load (ISO 3046/1, 1.0 power factor). In CHP mode, total efficiency (electrical + thermal recovery) reaches 86.8%.
What fuel quality does the G3520E require?
Pipeline-quality natural gas with a minimum Cat Methane Number of 80 and LHV of 35.64 MJ/Nm3. Fuel pressure at the engine control valve must be 11-35 kPag. Methane numbers down to 55 are possible with significant timing and power derates.

Compatible equipment

More in the Cat 3500 Series (Gas)

750–2,519 kW of natural gas power for cogeneration, distributed generation, and industrial baseload.

Similar models

Caterpillar Cat G3516H 2.0 MW liquid-cooled standby generator

Caterpillar

Cat G3516H

1982 kW natural gas with CAT G3516H V-16. 43.5% electrical efficiency. Cogeneration-ready. Best resale in class.

2.0 MW standby · Natural Gas · Liquid-cooled

1982 kW continuous natural gas generator with Cat G3516H V-16 engine. High-efficiency combined heat and power for industrial, utility, and distributed generation.

3-phasecogenerationdistributed-generation
Caterpillar Cat G3516H 2.0 MW liquid-cooled standby generator

Caterpillar

Cat G3516H

2027 kW natural gas with CAT G3516H V-16. Medium-voltage capable. Cogeneration-ready. Best resale in class.

2.0 MW standby · Natural Gas · Liquid-cooled

Up to 2027 kW natural gas generator with Cat G3516H V-16 engine. Continuous duty, low-emission gas power for cogeneration, distributed generation, and industrial applications.

EPA Stationary Spark Ignition3-phasecontinuous-dutycogeneration
Cummins Cummins C1000 N6 1 MW liquid-cooled standby generator

Cummins

Cummins C1000 N6

1000 kW natural gas with full Cummins vertical integration. QSK60G engine. Paralleling for multi-MW gas installations.

1 MW standby · Natural Gas · Liquid-cooled

1000 kW standby natural gas generator with QSK60G V16 engine. EPA NSPS certified, 36.4% electrical efficiency, remote radiator cooling, pipeline natural gas.

3-phasecommercial-standbyindustrial

Need service or parts for the Cat G3520E?

We service every major OEM and stock genuine parts for the most common models.