Cummins · Cummins D5 International Diesel

Cummins C55 D5

44 kW standby / 40 kW prime · Diesel · Liquid-cooled

44 kW / 55 kVA standby (40 kW / 50 kVA prime) 50 Hz diesel generator set from Cummins' international model range, with the Cummins 4BTAA3.3-G13 engine, for commercial applications.

Standby power
44 kW / 40 kW prime
Voltage options
230/400V, 240/415V
Frequency / Phase
50 Hz · 3-phase
Engine
Cummins 4BTAA3.3-G13
Alternator
UCI224C

Overview#

The Cummins C55 D5 is a 44 kW / 55 kVA standby (40 kW / 50 kVA prime) diesel generator set from Cummins' international model range, rated at 50 Hz.

The C55D5L variant of the C55 D5 uses the Cummins 4BTAA3.3-G13 engine, with the UCI224C as its standard alternator and the PS0600 as its standard controller.

Technical Specifications#

Power Ratings (50 Hz)

RatingkWkVA
Standby (ESP)4455
Prime (PRP)4050

Engine: Cummins 4BTAA3.3-G13

Standard alternator: UCI224C

Standard controller: PS0600

Operating Frequency The C55 D5 is a 50 Hz model from Cummins' international model range.

Our Service Experience#

Cummins 50 Hz diesel sets in the 44-66 kVA range are frequently encountered in international import applications, overseas facilities, and marine or offshore installations. Diesel engines in this class require careful attention to wet-stacking when the unit operates at light load or no-load for extended periods. We recommend exercising these units under load to maintain combustion temperatures adequate for clean operation.

For C55 D5 units brought to the United States for domestic use — typically through equipment relocation from international projects — we always verify the generator's original 50 Hz configuration before attempting commissioning. Running a 50 Hz generator at 60 Hz without reconfiguration causes overspeed, overvoltage, and potential engine damage.

Frequently Asked Questions#

Is the C55 D5 available for North American installations? The D5 series is Cummins' international 50 Hz export range. For North American 60 Hz standby in this power range, consult your Cummins distributor for the appropriate D6 model. Attempting to use a 50 Hz C55 D5 on a 60 Hz grid is not supported and will cause equipment damage.

What engine does the C55 D5 use? The C55D5L variant of the C55 D5 uses the Cummins 4BTAA3.3-G13 engine.

What voltage configurations does the C55 D5 support? Confirm available voltage options with your Cummins distributor for the specific regional variant.

How do I identify which Cummins 50 Hz model I have? Check the generator nameplate on the enclosure and the engine data plate. The nameplate will list the full Cummins model number, serial number, rated output in kVA, rated speed in rpm, and rated frequency in Hz. With the serial number, any Cummins distributor can pull the full configuration records.

FAQ#

What is the standby rating of the Cummins C55 D5?#

The C55 D5 is rated for 44 kW / 55 kVA standby output at 50 Hz.

What engine does the Cummins C55 D5 use?#

The C55D5L variant of the C55 D5 uses the Cummins 4BTAA3.3-G13 engine, as listed on Cummins' international 50 Hz rating card.

Can the Cummins C55 D5 be paralleled with other generators?#

Paralleling capability depends on the control system fitted to the specific installation. The standard controller listed for the C55 D5 is the PS0600. For multi-unit paralleling requirements, consult your Cummins distributor for available control options.

What fuel type does the Cummins C55 D5 use?#

The C55 D5 runs on diesel fuel. Confirm fuel specifications with Cummins or your distributor for the specific regional variant.

What voltage configurations does the C55 D5 support?#

Voltage options depend on the alternator specified for the specific regional variant; confirm them with your Cummins distributor.

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Cummins C55 D5

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Cummins C55 D5

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

84.2 hours(3.5 days)

Fuel consumption ≈ 2.38 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine does the Cummins C55 D5 use?
The C55D5L variant of the C55 D5 uses the Cummins 4BTAA3.3-G13 engine.
What are the standby and prime ratings of the C55 D5?
The C55 D5 is rated for 44 kW / 55 kVA standby and 40 kW / 50 kVA prime at 50 Hz.
Is the C55 D5 available for 60 Hz North American use?
The C55 D5 is listed only in Cummins' international 50 Hz rating card. For North American 60 Hz standby in this power range, consult your Cummins distributor for the appropriate D6 model. Attempting to use a 50 Hz unit on a 60 Hz grid will cause overspeed and equipment damage.
Can PowerGen service the C55 D5 in Northern California?
Yes. PowerGen serves the San Francisco Bay Area and broader Northern California. The C55 D5 is an international 50 Hz export model and uncommon in domestic installs, but our team handles Cummins diesel platforms including international variants. Contact us to confirm parts availability before scheduling.

Compatible equipment

Similar models

Cummins

Cummins C33 D5

26 kW / 33 kVA standby diesel at 50 Hz with the Cummins X3.3-G1 engine, an S0L2-P1 standard alternator and a PS0600 standard controller.

26 kW standby · Diesel · Liquid-cooled

26 kW / 33 kVA standby diesel generator from Cummins' international 50 Hz model range, with the Cummins X3.3-G1 engine, for commercial standby applications.

3-phasecommercial-standbyinternational-export
Cummins Cummins C80 D6 80 kW liquid-cooled standby generator

Cummins

Cummins C80 D6

80 kW standby diesel generator set that accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.

80 kW standby · Diesel · Liquid-cooled

80 kW standby, 72 kW prime EPA Tier 3 diesel generator set at 60 Hz with a Cummins QSB5-G13 engine and a standard cooling package for running at up to 50 °C (122 °F) ambient. Aluminum sound-attenuated enclosures available.

Tier 33-phasecommercial-standbylight-industrial
MTU MTU 4R0113 DS50 50 kW liquid-cooled standby generator

MTU

MTU 4R0113 DS50

50 kW diesel standby with mechanical injection John Deere 4045TF280. Simple maintenance, no ECU — robust cold-start, 4.6 gph full load.

50 kW standby · Diesel · Liquid-cooled

50 kW EPA Tier 3 diesel standby generator with John Deere 4045TF280 engine, 4.5 L 4-cylinder mechanical injection, 1800 rpm. UL 2200 offered, 50°C radiator.

Tier 33-phasecommercial-standbylight-industrial

Services for the Cummins C55 D5

Need service or parts for the Cummins C55 D5?

We service every major OEM and stock genuine parts for the most common models.