Cummins · Cummins D6 Commercial Diesel

Cummins C250 D6

250 kW standby · Diesel · Liquid-cooled

250 kW diesel standby generator with the EPA Tier 3 Cummins QSL9-G7 engine (8.8 L, in-line 6-cylinder) and Bosch high pressure common rail (HPCR) fuel system, for commercial and industrial standby applications.

Cummins Cummins C250 D6 generator — specifications and details
Standby power
250 kW
Voltage options
120/208V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 3-phase
Engine
Cummins QSL9-G7 · 8.8L
EPA / Emissions
Tier 3

Overview#

The Cummins C250 D6 is a 250 kW standby diesel generator set built on the Cummins QSL9-G7 engine, an 8.8-liter, in-line 6-cylinder turbocharged industrial diesel running at 1800 rpm for 60 Hz.

The QSL9-G7 features Bosch high-pressure common rail (HPCR) fuel injection, a Holset HX40 wastegated turbocharger, and a 24-valve cylinder head with four valves per cylinder for increased power with faster response and fuel economy. The engine sheet lists it as EPA Tier 3 / EU Stage IIIA / TA Luft compliant.

The C250 D6 suits large commercial standby applications including hospitals, data centers, office towers, and industrial facilities.

Our Service Experience#

On QSL9-G7 installations, the HPCR fuel injection system is the most critical maintenance item -- fuel quality directly affects injector life. We recommend fuel polishing and regular water separator service.

Ready to order this model?

Configure your Cummins C250 D6

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Cummins C250 D6

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

14.8 hours(0.6 days)

Fuel consumption ≈ 13.50 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine does the Cummins C250 D6 use?
The C250 D6 uses the Cummins QSL9-G7, an 8.8-liter, in-line 6-cylinder, turbocharged diesel rated at 1800 rpm for 60 Hz. The engine sheet lists it as EPA Tier 3 / EU Stage IIIA / TA Luft compliant. The QSL9 features Bosch high-pressure common rail (HPCR) fuel injection, a Holset HX40 wastegated turbocharger, a 24-valve cylinder head, and integrated fluid circuits that replace hoses.
Can PowerGen service the C250 D6 in Northern California?
Yes. PowerGen serves the San Francisco Bay Area, Silicon Valley, and broader Northern California with authorized Cummins service.

Compatible equipment

Similar models

Cummins Cummins C200 D6 200 kW liquid-cooled standby generator

Cummins

Cummins C200 D6

200 kW standby diesel generator set with a Cummins QSB7-G5 engine. PC 1.1 controller standard.

200 kW standby · Diesel · Liquid-cooled

200 kW standby (180 kW prime) 60 Hz diesel generator set with the Cummins QSB7-G5 engine, EPA Tier 3 emissions certification and the PC 1.1 standard controller.

Tier 33-phasecommercial-standbyindustrial
Cummins Cummins C275 D6 275 kW liquid-cooled standby generator

Cummins

Cummins C275 D6

275 kW standby diesel generator set with a Cummins QSL9-G9 engine, PCC 3300 control and EPA Tier 4 emissions certification.

275 kW standby · Diesel · Liquid-cooled

275 kW standby, 250 kW prime diesel generator set at 60 Hz with a Cummins QSL9-G9 engine, PCC 3300 control and EPA Tier 4 emissions certification, for commercial and industrial standby applications.

3-phasecommercial-standbylight-industrial
Cummins Cummins C250 N6 250 kW liquid-cooled standby generator

Cummins

Cummins C250 N6

250 kW natural gas generator set that accepts full rated load in a single step per NFPA 110 Type 10 (ten seconds). No diesel logistics.

250 kW standby · Natural Gas · Liquid-cooled

250 kW natural gas standby generator with Cummins GTA855E 14 L engine. PowerCommand 3.3 control, UL 2200 listed, NFPA 110 Type 10 Level 1/2 capable. EPA SI NSPS stationary emergency certified.

3-phaselarge-commercialhospital-medium

Services for the Cummins C250 D6

Need service or parts for the Cummins C250 D6?

We service every major OEM and stock genuine parts for the most common models.