Overview#
The Kohler 55REOZT4 is a 47-kilowatt standby (42 kW prime) EPA Tier 4 Final diesel mobile trailer generator powered by a Kohler KDI 3404 TCR engine at 1800 RPM. The 4-cylinder, 3.4-liter charge-air-cooled engine achieves Tier 4 Final compliance via cooled EGR and Diesel Oxidation Catalyst — no DPF required.
The 55REOZT4 uses a brushless rare-earth permanent-magnet alternator with Kohler's Fast-Response X excitation system, providing excellent voltage response and sustained short-circuit capability — the alternator can sustain 300% of rated current for up to 10 seconds to enable downstream breakers to clear faults without collapsing the field. The Decision-Maker 3500 paralleling controller enables synchronized parallel operation. A 386-liter (102-gallon) fuel tank provides a minimum 24 hours of runtime at prime rating.
The single-axle trailer is rated at 6,000 lb., DOT and Transport Canada compliant, with electric brakes and breakaway battery backup. Environmental containment is 125% for oil/coolant and 110% secondary for fuel.
Specifications#
| Spec | Value |
|---|---|
| Standby Power | 47 kW |
| Prime Power | 42 kW |
| Voltage | 120/208V, 120/240V, 277/480V, 347/600V |
| Frequency | 60 Hz |
| Engine | Kohler KDI 3404 TCR |
| Cylinders | 4 inline |
| Displacement | 3.4 L (207 cu. in.) |
| Aspiration | Turbocharged, Charge Air Cooled |
| Emissions | EPA Tier 4 Final (nonroad) |
| RPM | 1800 |
| Fuel | Ultra Low Sulfur Diesel / HVO / RD |
| Cooling | Liquid (unit-mounted radiator, 45°C ambient) |
| Fuel consumption — 100% load | 3.8 gph (standby) |
| Fuel consumption — 75% load | 2.9 gph (standby) |
| Fuel tank | 102 gal (386 L) — 24 hr minimum runtime |
| Sound level | 69 dB(A) @ 7 m (prime, full load) |
| Dimensions (L x W x H) | 98.6" x 44.1" x 94.4" |
| Controller | Decision-Maker 3500 |
Service & Maintenance#
Oil pan capacity with filter is 15.6 liters (16.5 quarts). Kohler specifies API CJ-4 or ACEA E6–E9 oil. The KDI 3404 TCR uses a primary 5-micron water-separator fuel filter; pay close attention to water-separator status during wet-season deployments in Northern California.
Our service experience#
PowerGen provides installation, maintenance, load bank testing, and emergency service for Kohler industrial generators throughout Northern California and the Central Valley.
FAQ#
What is the standby rating of the Kohler 55REOZT4?#
The 55REOZT4 is rated at 47 kW standby (58 kVA at 0.8 PF three-phase) at 120/208V. Prime power is 42 kW. All ratings are per Kohler spec sheet G5-414.
Is the 55REOZT4 a mobile or stationary generator?#
The 55REOZT4 is a trailer-mounted mobile generator, EPA Tier 4 Final certified for nonroad applications. A single-axle DOT/TC-compliant trailer with electric brakes is available as an option.
Does the 55REOZT4 require a DPF?#
No. The 55REOZT4 meets EPA Tier 4 Final without a Diesel Particulate Filter. Kohler uses cooled EGR and a Diesel Oxidation Catalyst to meet emissions requirements on the KDI 3404 TCR engine.
What is the sound level of the Kohler 55REOZT4?#
Per Kohler published specifications, the 55REOZT4 is rated at 69 dB(A) log average at 7 meters with full load at the prime rating.