Generac · SD Series (Industrial Diesel)

Generac SD035

35 kW standby / 32 kW prime · Diesel · Liquid-cooled

35 kW industrial diesel standby generator. Generac 3.4L turbocharged-aftercooled inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

Generac Generac SD035 generator — specifications and details
Standby power
35 kW / 32 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 346/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Generac 3.4L · 3.4L
Alternator
Generac 390 mm

Overview#

The Generac SD035 is a 35-kilowatt industrial diesel standby generator powered by Generac's own 3.4-liter turbocharged and aftercooled inline-four engine. Rated at 35 kW standby and 32 kW prime, the SD035 marks the transition from the Perkins-powered small diesel family to Generac's proprietary engine platform. The 3.4L engine's Bosch VE fuel injection system and 18.5:1 compression ratio deliver higher BMEP (118 psi) and a higher exhaust temperature (900°F) compared to the smaller Perkins units, reflecting the more demanding operating point. The generator is EPA Certified for Stationary Emergency applications.

Generac pairs the 3.4L engine with their 390 mm alternator featuring Class H insulation, synchronous brushless excitation, and a digital voltage regulator with ±0.25% steady-state regulation accuracy. The Digital H control panel provides NFPA 110 Level I and II programmable operation, Modbus communications, and a 7-day programmable exerciser. A 120 VAC engine coolant heater is standard equipment.

At 35 kW, this unit covers mid-size commercial standby loads: larger restaurants and food service operations, professional offices, small medical facilities, and light manufacturing. The single-phase 120/240 VAC configuration at 146 amps makes it practical for facilities with single-phase service that need 35 kW of emergency capacity.

Technical Specifications#

ParameterValue
Standby Rating35 kW / 44 kVA
Prime Rating32 kW / 39 kVA
Engine MakeGenerac
Displacement3.4 L (207.48 in³)
Cylinders4, In-Line
Bore x Stroke3.86 x 4.45 in (98 x 113 mm)
Compression Ratio18.5:1
AspirationTurbocharged/Aftercooled
Engine Speed1,800 RPM
Alternator ModelGenerac 390 mm
Insulation ClassH
Fuel TypeUltra Low Sulfur Diesel #2
Fuel Consumption (100%)3.1 gph
Fuel Consumption (75%)2.4 gph
Fuel Consumption (50%)1.7 gph
Fuel Consumption (25%)1.0 gph
Exhaust Flow342 cfm at rated output
Exhaust Temperature900°F (482°C)
Heat Rejection to Coolant96,000 BTU/hr
Combustion Air150 cfm
Open Set (no tank) L x W x H76.7 x 37.4 x 45.2 in
Open Set Weight (no tank)1,719 lbs
Max Ambient Temperature122°F (50°C)

Our Service Experience#

The Generac 3.4L engine platform in the SD035 and SD050 is one we see frequently in commercial standby applications in Northern California. The Bosch VE injection pump and pintle injectors are robust for standby-duty use but sensitive to fuel quality: contaminated or degraded diesel leads to injection system wear and misfiring under load. Annual fuel polishing is standard practice for any installation where the sub-base tank sits for more than six months between exercises.

Compared to the Perkins 2.22L in the smaller SD models, the 3.4L generates considerably more exhaust heat (900°F exhaust temperature) and requires adequate clearance for heat dissipation. Inspect the exhaust flex connector for cracking at each service visit; the higher exhaust temps accelerate flex connector wear. The 120 VAC coolant heater is more critical on this engine due to the higher thermal mass -- verify function before winter.

Frequently Asked Questions#

Is the SD035 available with IBC seismic certification? Yes. IBC seismic certification is an engineered option for the SD035, available per factory order. This is required for standby generator installations in California hospitals, essential facilities, and other occupancies subject to CBC/IBC seismic requirements.

What is the motor starting capability of the SD035? At 277/480 VAC with the standard 35 kW alternator and a 30% voltage dip, the SD035 can start 84 sKVA of motor load. With alternator upsizing options (up to 60 kW alternator), starting capability increases to 146 sKVA at 30% voltage dip. Three-phase 120/208 or 120/240 VAC configurations have lower starting capability; consult load calculations for motor-heavy applications.

What fuel tank options are available for the SD035? Sub-base UL 142 double-wall fuel tanks are available in 54, 132, 211, and 300 usable gallon sizes. At 3.1 gph full load, a 300-gallon tank provides approximately 96 hours of runtime at full standby load. Tank risers and extended fill options are available for installations where the standard height profile creates access issues.

Engineering specifications

Physical

Length
76.7 in
Width
37.4 in
Height
45.2 in
Dry weight
1,719 lb

Fuel system & runtime

Fuel use @ full load
3.1 GPH
Fuel use @ 75% load
2.4 GPH
Fuel use @ 50% load
1.7 GPH

Thermal & ventilation

Heat to coolant
96,000 BTU/hr
Exhaust flow
342 CFM
Exhaust temp
900 °F
Combustion air
150 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Generac SD035

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac SD035

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

83.6 hours(3.5 days)

Fuel consumption ≈ 2.39 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac SD035 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power output4,380+moderate
TurbochargerPower loss, excessive smoke under load, oil consumption15,000+moderate
BatteryFailed to start, slow cranking8,760+minor
Coolant heaterLow coolant temperature alarm, slow start in cold weather20,000+minor

Frequently Asked Questions

What engine does the Generac SD035 use?
The Generac SD035 uses a Generac-branded 3.4-liter, four-cylinder in-line turbocharged and aftercooled diesel engine running at 1800 RPM. The engine has a bore of 3.86 in (98 mm), stroke of 4.45 in (113 mm), and 18.5:1 compression ratio. The fuel injection is a Bosch VE distribution pump with pintle injectors rated at 2,100 psi.
What is the fuel consumption of the Generac SD035?
At standby rating, the SD035 consumes 3.1 gallons per hour at full load (100%), 2.4 gph at 75% load, 1.7 gph at 50% load, and 1.0 gph at 25% load. Total fuel pump flow (combustion plus return) is 3.57 gph. The fuel pump lift is rated at 3 feet.
What voltages are available for the SD035?
The SD035 is available in single-phase 120/240 VAC (146 amps at 1.0 pf) and three-phase configurations: 120/208 VAC (121 amps), 120/240 VAC (105 amps), 277/480 VAC (53 amps), and 346/600 VAC (42 amps), all at 0.8 power factor.
What are the dimensions and weight of the SD035?
The open-set SD035 without a sub-base fuel tank measures 76.7 x 37.4 x 45.2 inches and weighs 1,719 lbs. With sub-base tanks the height increases to 85.7 inches for the 300-gallon configuration. The SD035 is slightly longer than the Perkins-based 10-20 kW models, reflecting the larger 3.4L engine.
What is the alternator model on the SD035?
The SD035 uses a Generac 390 mm alternator with 4 poles, Class H insulation on both rotor and stator, synchronous brushless excitation, and a single sealed cartridge bearing. THD is less than 5% on three-phase configurations. The voltage regulator is digital with regulation accuracy of ±0.25% steady state.

Compatible equipment

More in the SD Series (Industrial Diesel)

Generac's broadest diesel standby lineup — 10 to 1500 kW across four engine families for commercial and industrial applications.

Similar models

Generac Generac SD020 20 kW liquid-cooled standby generator

Generac

Generac SD020

20 kW industrial diesel with Perkins engine. 10-15% below Kohler at comparable kW. NFPA 110 Level I/II ready.

20 kW standby · Diesel · Liquid-cooled

20 kW industrial diesel standby generator. Perkins 2.2L turbocharged inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial
Generac Generac SD050 50 kW liquid-cooled standby generator

Generac

Generac SD050

50 kW industrial diesel with Generac 3.4L engine. 10-15% below Kohler pricing. Digital controller, NFPA 110 ready.

50 kW standby · Diesel · Liquid-cooled

50 kW industrial diesel standby generator. Generac 3.4L turbocharged-aftercooled inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial
Generac Generac SG035 35 kW liquid-cooled standby generator

Generac

Generac SG035

35 kW natural gas/LP with Generac 4.5L engine. No on-site fuel storage required. 10-15% below Kohler gas equivalent.

35 kW standby · Natural Gas · Liquid-cooled

35 kW standby natural gas/LP generator with Generac 4.5L naturally aspirated inline-4 engine. Power Zone Pro controller, NFPA 110 Level 1 compliant, UL 2200 listed, EPA certified stationary emergency.

EPA Stationary Spark Ignition3-phasecommercial-standbylight-industrial

Need service or parts for the Generac SD035?

We service every major OEM and stock genuine parts for the most common models.