Above 1 MW, standby power architecture typically shifts from a single genset to a paralleled array of two or more units (often configured N+1). The mechanical/electrical room footprint, fuel storage volume, and combustion-air ventilation become significant building-design constraints. EPA Tier 4 Final is universal at this size for diesel; aftertreatment maintenance is a non-trivial part of the lifecycle cost.
50 models in this category.
Need help selecting a generators 1,000–2,000 kw?
Our application engineers help size, spec, and source backup power for commercial, industrial, and mission-critical sites.
Open Basler controller + Mitsubishi V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component independence matter.
1000 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12H-Y2PTAW-1 37.1L V12 engine, Stamford S6L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1250-01
Open Basler controller + Mitsubishi V12 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and open-architecture components matter.
1250 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12R-Y2PTAW-1 49.0L V12 engine, Stamford S6L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1600-01
Open Basler controller + Mitsubishi V16 engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and non-proprietary components matter.
1600 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S16R-Y2PTAW-1 65.4L V16 engine, Stamford S7L1D alternator, DSE DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star NG1050-01
Open Basler controller + PSI V16 engine + Stamford alternator — no proprietary lock-in. 1 MW gas class without OEM dealer dependency.
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
1050 kW natural gas standby for data centers, campus power, and utility-scale gas applications where component independence matters.
1050 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.
Open Basler controller + PSI V16 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
900 kW prime natural gas for continuous-duty data center, CHP, and utility-scale applications needing 24/7 gas-fueled power.
900 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.
Open Basler controller + PSI high-output V16 engine + Stamford alternator — no proprietary lock-in. 1.25 MW gas class without OEM dealer dependency.
1.3 MW standby · Natural Gas · Liquid-cooled
1250 kW natural-gas-only standby for data centers and utility-scale facilities where gas-fueled backup and component independence matter.
1250 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 53LHO high-output V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V. LP not available.
1000 kW diesel with CAT 3512 V-12. Best resale value in class. ~200 US dealers with parts availability back decades.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for Tier III data centers, large hospitals, and industrial campuses with CAT fleet.
1000-1400 kVA diesel generator with Cat 3512 V-12 engine. 51.8L displacement, Woodward governor, continuous/prime/standby ratings.
3-phasecommercial-standbyindustrial
Caterpillar
Cat 3512B
1500 kW diesel with CAT 3512B V-12. Best resale -- retains 15-25% more than Cummins/MTU. Deepest parts network.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
1230-1500 kW diesel generator with Cat 3512B V-12 engine. EUI fuel system, EMCP 4.2B controller, mission-critical and standby ratings.
3-phasecommercial-standbymission-critical
Caterpillar
Cat 3516
1600 kW diesel with CAT 3516 V-16. Best resale -- retains 15-25% more than competitors. ~200 US dealer network.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW diesel standby for large data centers, hospitals, and industrial campuses with CAT fleet standardization.
1600 kW diesel generator with Cat 3516 turbocharged V-16 engine. Mission-critical platform for data centers, hospitals, and large industrial standby and prime power.
3-phasedata-centerhospital
Caterpillar
Cat C32
1000 kW diesel with CAT C32 V-12. Best resale value in class. ~200 US dealers. Paralleling for multi-MW.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for Tier III data centers, large hospitals, and industrial campuses with CAT fleet.
1000 kW diesel standby generator with Cat C32 ACERT V-12 engine. Mission-critical platform for data centers, hospitals, and large campus power.
Tier 23-phasedata-centerhospital
Caterpillar
Cat C32B
1500 kW diesel with CAT C32B V-12. EPA Tier 2. Best resale in class. ~200 US dealers. Paralleling for multi-MW.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, hospitals, and mission-critical campus infrastructure.
1982 kW natural gas with CAT G3516H V-16. 43.5% electrical efficiency. Cogeneration-ready. Best resale in class.
2.0 MW standby · Natural Gas · Liquid-cooled
1982 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and utility power.
1982 kW continuous natural gas generator with Cat G3516H V-16 engine. High-efficiency combined heat and power for industrial, utility, and distributed generation.
3-phasecogenerationdistributed-generation
Caterpillar
Caterpillar 3512C
1500 kW diesel with CAT 3512C V-12. EPA Tier 4 Final. Best resale value in class. ~200 US dealers.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, hospitals, and emission-sensitive industrial sites.
The Caterpillar 3512C is a 1500 kW standby diesel generator. 51.8L V12 ATAAC, 14.7:1 compression, EPA Tier 2. Fuel: 104.6 gal/hr at full load. Medium-voltage outputs to 13,800V for mission-critical applications.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins C1000 N6
1000 kW natural gas with full Cummins vertical integration. QSK60G engine. Paralleling for multi-MW gas installations.
1 MW standby · Natural Gas · Liquid-cooled
1000 kW natural gas standby for Tier III data centers, large campuses, and utility peak shaving on gas.
1340 kW diesel with legendary KTA50 engine. Full Cummins vertical integration. 10-15% below CAT 3512 class.
1.3 MW standby · Diesel · Liquid-cooled
1340 kW diesel standby for Tier III+ data centers, large hospitals, and heavy industrial plants.
1340 kW standby / 1200 kW prime diesel generator at 50 Hz. KTA50-GS8 50.3L V16 PT fuel injection, 2-pump 2-loop cooling. Legacy Cummins platform for data center, industrial, hospital, and mining standby applications.
3-phasedata-centerhospital-large
Cummins
Cummins QSK38
1160 kW diesel with QSK38 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT.
1.2 MW standby · Diesel · Liquid-cooled
1160 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
1160 kW standby / 965 kW prime diesel generator with QSK38-G5 37.7L V12 MCRS engine. EPA Tier 2, 2P2L cooling, 24V starting. Engine dimensions 2081 x 1492 x 1860 mm, dry weight 4100 kg.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins QSK50
1500 kW diesel with QSK50 engine. Full Cummins vertical integration. Paralleling for multi-MW. 10-15% below CAT 3512.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier IV data centers, university campuses, and major industrial plants.
1500 kW standby / 1365 kW prime diesel generator with QSK50-G4 50.3L V16 MCRS engine. EPA Tier 2 and TA Luft compliant, 2P2L cooling, 24V starting. Engine dimensions 4674 x 2468 x 3100 mm, dry weight 7429 kg.
Tier 23-phasedata-centerhospital-large
Generac
Generac SD1250
1250 kW industrial diesel with Mitsubishi engine. Competitive pricing vs CAT/Cummins. Paralleling for multi-MW systems.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
Factory-direct megawatt-class gas at 15-30% below major brands. PSI 52.3L V16 engine + DSE controller — no proprietary lock-in.
1.1 MW standby · Natural Gas · Liquid-cooled
1,050 kW (1 MW) natural gas standby for data centers, hospitals, industrial campuses, and utility-scale backup.
1,050 kW natural gas stationary standby generator. PSI 52.3L V16 turbocharged engine, Stamford AVK alternator, DSE 7420 MKII. Natural gas only. Made in USA.
First MW-class unit in the HMW lineup — MTU 16V2000 32L 16-cylinder with 30,000-hour TBO. Standard for hyperscale data center 1 MW bus design.
1 MW standby · Diesel · Liquid-cooled
1 MW+ critical standby for hyperscale data center 1 MW bus rows, large hospital main plants, and mission-critical industrial utility in NFPA 110 Level 1 applications.
1020 kW MTU 2000-series diesel generator. Exceeds 1 MW standby. NFPA 110 Level 1, seismic certified. US manufactured in Olathe, Kansas.
Tier 23-phaseindustrial-standbydata-center
Hipower Systems
Hipower HMW-1205
MTU 16V2000 at 1,205 kW — top of the 2000 series before entering the 4000 series. Maximum output for a single 16V2000 unit with 30,000-hour TBO.
1.2 MW standby · Diesel · Liquid-cooled
1.2 MW single-unit critical standby for hyperscale data center rows, large hospital main plants, and transmission-level utility backup.
1205 kW MTU 2000-series diesel generator. NFPA 110 Level 1, seismic certified, 200 mph wind rated. US manufactured in Olathe, Kansas.
Tier 23-phaseindustrial-standbydata-center
Hipower Systems
Hipower HMW-1550
MTU 4000 series — the industrial benchmark for 1.5 MW+ standby. 52L 12-cylinder V with 30,000-hour TBO. Used in defense, hyperscale, and utility generation.
1.5 MW standby · Diesel · Liquid-cooled
1.5 MW critical standby for hyperscale data centers, major hospital campuses, military installations, and electric utility backup in NFPA 110 Level 1 applications.
1550 kW MTU 4000-series diesel generator. NFPA 110 Level 1, seismic certified, 200 mph wind rated. US manufactured in Olathe, Kansas.
Tier 23-phaseindustrial-standbydata-center
Hipower Systems
Hipower HMW-1730
MTU 12V4000 at 1.7 MW — maximum output for the 12-cylinder 4000 series. 30,000-hour TBO at 1.7 MW single-unit standby.
1.7 MW standby · Diesel · Liquid-cooled
1.7 MW critical standby for hyperscale data centers, military bases, and large hospital campuses requiring NFPA 110 Level 1 with .
1730 kW MTU 4000-series diesel generator. NFPA 110 Level 1, seismic certified, 200 mph wind rated. US manufactured in Olathe, Kansas.
Tier 23-phaseindustrial-standbydata-center
Hipower Systems
Hipower HMW-1975
MTU 16V4000 near-2 MW — 68L 16-cylinder V with 30,000-hour TBO. The largest single-unit generator class deployed at hyperscale cloud data centers.
2.0 MW standby · Diesel · Liquid-cooled
Near-2 MW critical standby for hyperscale data centers, transmission substations, military bases, and large campus essential systems.
1975 kW MTU 4000-series diesel generator. Near-2 MW single unit. NFPA 110 Level 1, seismic certified. US manufactured in Olathe, Kansas.
Tier 23-phaseindustrial-standbydata-center
Hipower Systems
Hipower HNI-1000
Broadest CARB-certified natural gas lineup from a Tier 2 manufacturer — 30 to 1000 kW with PSI and Origin engines.
1 MW standby · Natural Gas / LPG · Liquid-cooled
California 1 MW natural gas standby for data centers, hospitals, and industrial facilities where CARB certification is mandatory and Big 4 pricing is not justified.
1000 kW (1 MW) standby natural gas generator. Flagship HNI series unit. CARB certified for California large-facility natural gas standby.
Over 1 MW of mobile diesel power — Volvo TWD-powered, Tier 4 Final, for data centers, substations, and major construction.
1.1 MW standby · Diesel · Liquid-cooled
Data center emergency backup, substation maintenance, and large construction requiring over 1 MW of mobile standby power.
1250 kVA (1088 kW standby) mobile diesel generator with Volvo TWD1644GE family engine. Tier 4 Final. Over 1 MW of mobile standby power.
Tier 4 Final3-phaseconstructionrental-fleet
Hipower Systems
Hipower HRVW-1375
Flagship mobile diesel power — 1,210 kW standby, Volvo TWD engine, Tier 4 Final, for mission-critical and large-scale rental deployment.
1.2 MW standby · Diesel · Liquid-cooled
Data center emergency backup, major substation maintenance, and large-scale construction requiring over 1.2 MW of mobile standby power.
1375 kVA (1210 kW standby) mobile diesel generator with Volvo TWD-family engine. Tier 4 Final. Flagship mobile unit — over 1.2 MW of standby power.
Tier 4 Final3-phaseconstructionrental-fleet
Kohler
Kohler 1250REOZMD
1280 kW diesel standby -- Mitsubishi S12R-Y2PTAW-1, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.3 MW standby · Diesel · Liquid-cooled
1280 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1280 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 1250ROZMC
1120 kW diesel standby -- Mitsubishi S12R V12 turbo, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.1 MW standby · Diesel · Liquid-cooled
1120 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1120 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1600REOZMD
1600 kW industrial diesel -- Mitsubishi S16R-Y2PTAW-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1600 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
1560 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1560 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1750REOZMD
1780 kW industrial diesel -- Mitsubishi S16R-Y2PTAW2-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.8 MW standby · Diesel · Liquid-cooled
1780 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1780 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
1760 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1760 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
1250 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1250 kW EPA Tier 4 Final diesel industrial standby generator. Dual-certified (emergency and non-emergency) for mission-critical and prime power applications.
Data center continuous power at 1,600 kW DCCP. Diesel at 111 gph, flagship 12-cyl, HVO renewable fuel compatible.
1,750 kW standby / 1,600 kW DCCP diesel generator from MTU (Rolls-Royce). 57.2L V12 engine, EPA Tier 2 + SCAQMD, 380-13,800V. Maximum continuous output from the 12-cylinder Series 4000.