Triton Power · TP-JD

Triton Power TP-JD50-T4F

50 kW standby / 45 kW prime · Diesel · Liquid-cooled

50 kW Tier 4 Final diesel generator with John Deere 3029HG530 engine. UL2200-listed for commercial standby with 92.5-gallon integral fuel tank.

Triton Power Triton Power TP-JD50-T4F generator — specifications and details
Standby power
50 kW / 45 kW prime
Voltage options
120/208V, 277/480V, 120/240V
Frequency / Phase
60 Hz · 1/3-phase
Engine
John Deere 3029HG530 · 2.9L
EPA / Emissions
Tier 4 Final
Alternator
Leroy Somer LSA 42.3 L9

Overview#

The Triton Power TP-JD50-T4F is a 50 kW diesel standby generator powered by the John Deere 3029HG530 turbocharged three-cylinder engine (2.9 L displacement) and paired with a Leroy Somer LSA 42.3 L9 alternator. This unit meets EPA Tier 4 Final emissions standards for nonroad applications via PowerTech EWX direct injection and DOC/DPF aftertreatment. The 92.5-gallon integral fuel tank with 125% fluid containment supports extended runtime without external fuel storage.

Available in both single-phase (40 kW standby at 120/240V) and three-phase (50 kW standby at 277/480V) configurations, the unit features a Deep Sea Electronics DSE7420 controller with comprehensive monitoring. Fuel consumption is rated at 11.2 L/hr (2.96 GPH) at full load.

Our service experience#

The John Deere 3029HG530 engine platform is widely supported through John Deere's dealer network, giving this Triton unit a servicing advantage in Northern California. At 50 kW standby, the TP-JD50-T4F serves the mid-range commercial market where units from Kohler, Generac, and Cummins typically dominate, but at a lower acquisition cost. The Tier 4 Final aftertreatment (DOC/DPF) adds maintenance complexity compared to Tier 2/3 units — periodic DPF regeneration monitoring is required — but delivers the emissions compliance needed for nonroad mobile applications.

Engineering specifications

Physical

Length
124.4 in
Width
46.1 in
Height
70.9 in
Dry weight
4,200 lb

Acoustic

Sound @ 7m, full load
66 dBA

Fuel system & runtime

Integral fuel tank
92.5 gal
Fuel use @ full load
2.96 GPH
Fuel use @ 75% load
2.46 GPH
Fuel use @ 50% load
1.95 GPH

Ready to order this model?

Configure your Triton Power TP-JD50-T4F

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-JD50-T4F

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

40.5 hours(1.7 days)

Fuel consumption ≈ 2.28 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine powers the TP-JD50-T4F?
The TP-JD50-T4F uses a John Deere 3029HG530 turbocharged three-cylinder engine with 2.9 L displacement, running at 1800 RPM.
What is the fuel consumption at full load?
At full load the unit consumes 2.96 GPH of diesel. Consumption drops to 2.46 GPH at 75% load and 1.95 GPH at 50% load.
Does the TP-JD50-T4F meet Tier 4 Final emissions requirements?
Yes. The unit meets EPA Tier 4 Final emissions standards through John Deere PowerTech EWX direct injection combined with DOC/DPF aftertreatment.
What voltage options are available, and does the unit include a fuel tank?
The generator is available in 120/240V single-phase, 120/208V three-phase, and 277/480V three-phase. It includes a 92.5-gallon integral fuel tank with 125% fluid containment.

Why we recommend Triton Power

Triton Power is our value brand for mobile and portable diesel generators, and an emerging option for industrial standby. When MQ Power's pricing is a stretch or lead times are too long, Triton delivers comparable capability at a lower price point with faster availability.

We are developing our Triton Power sales relationship and building fleet experience. Every engine platform Triton uses — Perkins, John Deere, Kubota, Scania, Volvo — is one we already service daily across other brands. Triton's open architecture means our technicians can maintain these units with standard tooling and widely available parts.

See all Triton Powergenerators →

Similar models

Triton Power Triton Power TP-K30-T4i-UL 30 kW liquid-cooled standby generator

Triton Power

Triton Power TP-K30-T4i-UL

30 kW standby · Diesel · Liquid-cooled

30 kW diesel generator with Kubota V3300-E3BG-CHN-1 engine. UL2200-listed for commercial standby and light industrial applications.

3-phasecommercial-standbysmall-business
Triton Power Triton Power TP-P80-T3-UL 80 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P80-T3-UL

80 kW standby · Diesel · Liquid-cooled

80 kW Tier 3 diesel generator with Perkins 1104D-E44TAG1 engine. UL2200-listed for commercial standby and institutional applications.

Tier 33-phasecommercial-standbyeducation
Triton Power Triton Power TP-P100-T3-UL 100 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P100-T3-UL

100 kW standby · Diesel · Liquid-cooled

100 kW Tier 3 diesel generator with Perkins 1104D-E44TAG2 engine. UL2200-listed for commercial and institutional standby applications.

Tier 33-phasecommercial-standbyhealthcare

Need service or parts for the Triton Power TP-JD50-T4F?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: