Winco · DR Series

Winco DR100F4

100 kW standby / 90 kW prime · Diesel · Liquid-cooled

100 kW standby diesel generator with FPT engine and Stamford alternator. DR series enclosed. US-made.

Winco Winco DR100F4 generator — specifications and details
Standby power
100 kW / 90 kW prime
Voltage options
277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
FPT Industrial N67 TM1 · 6.7L
EPA / Emissions
Tier 3

Overview#

The Winco DR100F4 is a 100 kW standby diesel generator powered by an FPT Industrial N67 TM1 6.7-liter six-cylinder turbocharged diesel engine with a Stamford alternator. A three-phase-only unit (277/480V), it is one of the larger models in Winco's enclosed DR diesel standby series. EPA Tier III certified (standby). 100% US-made in Le Center, Minnesota since 1927.

At 100 kW, the DR100F4 is serious commercial infrastructure — serving buildings with significant electrical loads, life-safety systems, and code-mandated backup power requirements. The DR series enclosure provides outdoor-ready installation with sub-base fuel tank and automatic start capability.

The American Manufacturing Advantage#

Winco has manufactured generators in Le Center, Minnesota since 1927 — a continuous US manufacturing record unmatched in the industry. At 100 kW, the DR100F4 uses an FPT Industrial N67 six-cylinder engine and a Stamford alternator, both globally non-proprietary and independently supported.

For federal contractors, municipal utilities, healthcare systems, and educational institutions with Buy American Act or procurement mandate requirements, the DR100F4 qualifies as a US-manufactured product at a competitive price point. The FPT N67 engine is serviced through CNH Industrial's global dealer network (Case IH, New Holland, Iveco) — a distribution network that reaches even rural areas where Winco's own dealer presence is minimal.

Service & Maintenance#

Oil and fuel filter changes every 500 hours or annually — the annual interval is critical for standby units where diesel sits in tanks and degrades. The FPT N67 TM1 six-cylinder engine has a larger oil sump and filter capacity than smaller four-cylinder platforms; consumable costs are proportionally higher. Engine consumables are available through CNH Industrial dealers and standard diesel parts suppliers.

Stamford alternator maintenance covers brush wear, bearing condition, and winding insulation — routine tasks for any qualified generator technician. Transfer switch contacts should be exercised weekly. Major overhaul at 20,000 hours.

Our Service Experience#

PowerGen services Winco DR units throughout the Bay Area and Northern California. The FPT Industrial N67 and Stamford components mean we source parts through standard diesel channels — the same supply network we use for Cummins and Caterpillar. For clients with Buy American requirements or strong preferences for US-made standby infrastructure, the DR100F4 delivers 100 kW of reliable diesel standby from a proven American manufacturer.

Engineering specifications

Acoustic

Enclosure
Sound-attenuated

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Winco DR100F4

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Winco DR100F4

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

37.0 hours(1.5 days)

Fuel consumption ≈ 5.40 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Winco DR100F4 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel filterExtended standby fuel degradation — change annually regardless of hours500+minor
Starting batteryCapacity loss in standby — float charge, test annually4,380+minor
Transfer switch contactsOxidation on standby generators — exercise weekly to maintain contact quality8,760+minor

Frequently Asked Questions

What is the standby kW rating of the DR100F4?
The DR100F4 is rated at 100 kW standby. It is a three-phase-only unit (277/480V).
What engine does the DR100F4 use?
The DR100F4 uses an FPT Industrial N67 TM1 6.7-liter six-cylinder turbocharged diesel engine from CNH Industrial. The N67 is a widely deployed industrial platform used across Case IH, New Holland, and other CNH equipment lines worldwide.
What makes Winco different from Generac or Kohler?
Winco uses non-proprietary FPT Industrial engines and Stamford alternators — both globally supported components that any qualified diesel technician can service. Winco has manufactured 100% in Le Center, Minnesota since 1927. Generac and Kohler use proprietary engines and offer connected monitoring platforms and denser dealer networks, but require proprietary parts and service.
What emissions tier is the DR100F4?
The DR100F4 carries EPA Tier III certification for standby applications. The FPT N67 TM1 is a Tier III engine — standby generators in this class carry Tier III certification under EPA standby exemption rules.
Where are Winco generators made?
100% in Le Center, Minnesota. Winco has operated at that US facility continuously since 1927, making it America's oldest generator manufacturer.
What are the service intervals for the DR100F4?
Oil and fuel filter changes every 500 hours or annually. Air filter inspection at 500 hours. Major overhaul at 20,000 hours. Transfer switch contacts should be exercised weekly during standby to prevent oxidation.
Who services Winco generators in Northern California?
PowerGen services Winco DR units throughout the Bay Area and Northern California. The FPT Industrial N67 engine and Stamford alternator are non-proprietary — parts come through standard diesel supply chains, giving us full service capability without a dedicated Winco dealer.

More in the DR Series

USA-made Tier 4 diesel standby in enclosed packages — 13 to 175 kW on FPT and Isuzu engines.

Similar models

Winco Winco DR90F4 86 kW liquid-cooled standby generator

Winco

Winco DR90F4

100% US-made diesel standby with Stamford alternator and non-proprietary engines — serviceable by anyone, not locked to a dealer network.

86 kW standby · Diesel · Liquid-cooled

90 kW standby diesel generator with FPT engine and Stamford alternator. DR series enclosed. US-made.

Tier 33-phasecommercial-standby
Winco Winco DR130F4 130 kW liquid-cooled standby generator

Winco

Winco DR130F4

100% US-made diesel standby with Stamford alternator and non-proprietary engines — serviceable by anyone, not locked to a dealer network.

130 kW standby · Diesel · Liquid-cooled

130 kW standby diesel generator with FPT engine and Stamford alternator. DR series enclosed. US-made.

Tier 33-phasecommercial-standby
Gillette Gillette SPD-1000 100 kW liquid-cooled standby generator

Gillette

Gillette SPD-1000

Factory-direct at 15-30% below major brands. Perkins engine + DSE controller — no proprietary lock-in. 3-7 day lead times.

100 kW standby · Diesel · Liquid-cooled

100 kW stationary diesel standby generator with Perkins 1104D-E44TAG2 engine. Made-in-USA with Stamford UCI274D alternator and DSE 7420 MKII controller.

Tier 33-phasecommercialtelecom

Need service or parts for the Winco DR100F4?

We service every major OEM and stock genuine parts for the most common models.