Triton Power · TP-F

Triton Power TP-F250-T3-UL

260 kW standby / 236 kW prime · Diesel · Liquid-cooled

260 kW Tier 3 diesel generator with FPT C87TE3F.F550 engine. UL2200-listed for commercial and industrial standby applications.

Triton Power Triton Power TP-F250-T3-UL generator — specifications and details
Standby power
260 kW / 236 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
FPT Industrial C87TE3F.F550 · 8.7L
EPA / Emissions
Tier 3
Alternator
Leroy Somer LSA46.3M7

Overview#

The Triton Power TP-F250-T3-UL is a 260 kW diesel standby generator powered by the FPT Industrial C87TE3F.F550 engine — built on the proven CURSOR 9 platform. This 8.7 L inline six-cylinder with common rail fuel injection, turbocharging, and aftercooling delivers 260 kW standby / 236 kW prime. The unit is paired with a Leroy Somer LSA46.3M7 alternator, carries UL2200 listing, and meets EPA Tier 3 for emergency stationary applications.

This is a three-phase-only unit available at 120/208V and 277/480V. Fuel consumption is 59.9 L/hr (15.83 GPH) at full load, dropping to 34.8 L/hr (9.19 GPH) at half load.

The FPT CURSOR 9 advantage#

FPT Industrial (formerly Fiat Powertrain Technologies, now part of Iveco Group) builds the CURSOR engine family for heavy truck, marine, and power generation applications. The C87 designation indicates the CURSOR 9 platform — an 8.7 L common-rail diesel with strong torque characteristics and good transient load response. While less common in North American generators than Perkins or Cummins, the FPT engine offers competitive fuel efficiency and an expanding dealer network.

Our service experience#

The 250 kW class bridges the gap between the Perkins 1106D platform (maxing out around 200 kW) and the larger Perkins 1700/2200 series. The FPT CURSOR 9 fills this niche with a single-displacement solution that avoids the transition to a significantly larger engine block. In our Northern California territory, we see increasing adoption of FPT-powered generators as the brand builds out its North American service network.

Engineering specifications

Physical

Length
143 in
Width
57 in
Height
82 in
Dry weight
7,500 lb

Acoustic

Sound @ 7m, full load
68 dBA

Fuel system & runtime

Integral fuel tank
185 gal
Fuel use @ full load
15.83 GPH
Fuel use @ 75% load
12.84 GPH
Fuel use @ 50% load
9.19 GPH

Ready to order this model?

Configure your Triton Power TP-F250-T3-UL

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-F250-T3-UL

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

15.1 hours(0.6 days)

Fuel consumption ≈ 12.21 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine powers the Triton TP-F250-T3-UL?
The TP-F250-T3-UL uses an FPT Industrial C87TE3F.F550 engine from the CURSOR 9 platform — an 8.7 L inline six-cylinder with common rail fuel injection, turbocharging, and aftercooling, producing 290 kWm (388.9 HP) at 1800 RPM.
What is the fuel consumption of the TP-F250-T3-UL?
Full load consumption is 15.83 GPH (59.9 L/hr), 75% load is 12.84 GPH (48.6 L/hr), and 50% load is 9.19 GPH (34.8 L/hr).
Why does Triton use an FPT engine instead of Perkins at 250 kW?
The 250 kW class sits between the Perkins 1106D (maxing out around 200 kW) and the larger Perkins 2200 series. The FPT CURSOR 9 at 8.7 L fills this gap with a single-displacement solution that avoids transitioning to a significantly larger engine block.
Is the TP-F250-T3-UL UL listed?
Yes, the TP-F250-T3-UL carries UL2200 listing and meets EPA Tier 3 for emergency stationary applications. It is a three-phase-only unit available at 277/480V and 120/208V.

Why we recommend Triton Power

Triton Power is our value brand for mobile and portable diesel generators, and an emerging option for industrial standby. When MQ Power's pricing is a stretch or lead times are too long, Triton delivers comparable capability at a lower price point with faster availability.

We are developing our Triton Power sales relationship and building fleet experience. Every engine platform Triton uses — Perkins, John Deere, Kubota, Scania, Volvo — is one we already service daily across other brands. Triton's open architecture means our technicians can maintain these units with standard tooling and widely available parts.

See all Triton Powergenerators →

Similar models

Triton Power Triton Power TP-P200-T3-UL 200 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P200-T3-UL

200 kW standby · Diesel · Liquid-cooled

200 kW Tier 3 diesel generator with Perkins 1106D-E70TAG5 engine. UL2200-listed for commercial, healthcare, and government standby.

Tier 33-phasecommercial-standbyhealthcare
Triton Power Triton Power TP-S300-T4F 300 kW liquid-cooled standby generator

Triton Power

Triton Power TP-S300-T4F

300 kW standby · Diesel · Liquid-cooled

300 kW Tier 4 Final diesel generator with Scania DC13 084A engine. UL2200-listed with 209-gallon fuel tank and 125% fluid containment.

Tier 4 Final3-phasecommercial-standbyindustrial-light

Triton Power

Triton Power TP-F300-T3-UL

300 kW standby · Diesel · Liquid-cooled

300 kW Tier 3 UL-listed diesel generator with FPT C87TE4F.F550 engine. For commercial and industrial standby applications.

Tier 33-phasecommercial-standbyindustrial

Need service or parts for the Triton Power TP-F250-T3-UL?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: