Generac · SD/MD Series (Industrial Diesel)

Generac SD2000/MD2000

2000 kW standby · Diesel · Liquid-cooled

2000 kW diesel industrial standby generator. Mitsubishi 65.4L V16 turbocharged/intercooled, EPA Tier 2 Certified Stationary Emergency.

Generac Generac SD2000/MD2000 generator — specifications and details
Standby power
2000 kW
Voltage options
277/480V, 346/600V
Frequency / Phase
60 Hz · 3-phase
Engine
Mitsubishi 65.4L · 65.4L
EPA / Emissions
Tier 2
Alternator
Generac

Overview#

The Generac SD2000/MD2000 is a 2,000-kilowatt industrial diesel generator powered by a Mitsubishi S16R-Y2PTAW2-1 65.4-liter V16 turbocharged and intercooled diesel engine producing 2,923 horsepower. This unit is EPA Tier 2 Certified for Stationary Emergency applications and represents the top output of Generac's Mitsubishi-powered diesel platform. Above this power level, Generac transitions to Baudouin engines in the SDMD2250 and larger models.

The SD and MD designations represent different enclosure and configuration options on the same power platform. The SDMD2000 is rated at 2,500 kVA standby at 0.8 power factor and supports paralleling through Generac's Modular Power Systems.

Our Service Experience#

The SDMD2000 pushes the Mitsubishi S16R platform to its maximum output, which means the engine operates at higher specific loading than the SD1500 and SD1750 using the same block. Fuel consumption at full load is substantial, and we recommend duplex fuel filtration and regular fuel quality testing for standby applications. The V16 configuration requires careful attention to cylinder balance and turbocharger performance at this output level. Given the critical nature of facilities served at 2 MW capacity, we recommend comprehensive service contracts with guaranteed emergency response times.

Engineering specifications

Fuel system & runtime

Fuel use @ full load
140 GPH
Fuel use @ 75% load
105 GPH
Fuel use @ 50% load
70 GPH

Ready to order this model?

Configure your Generac SD2000/MD2000

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac SD2000/MD2000

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

1.9 hours(0.1 days)

Fuel consumption ≈ 108.00 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac SD2000/MD2000 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, injector fouling, filter clogging, reduced power output4,380+moderate
TurbochargerPower loss, excessive smoke under load, oil consumption15,000+moderate
High pressure common rail injection systemRough running, misfiring cylinders, fuel rail pressure faults20,000+severe
Battery (24 VDC system)Failed to start, slow cranking8,760+minor

Frequently Asked Questions

What engine does the Generac SDMD2000 use?
The SDMD2000 uses a Mitsubishi S16R-Y2PTAW2-1 65.4-liter (3,989 cubic inch) V16 turbocharged and intercooled diesel engine running at 1800 RPM. The engine features a 6.69-inch (170 mm) bore, 7.09-inch (180 mm) stroke, and 14.0:1 compression ratio. It produces 2,923 horsepower at standby rating and is EPA Tier 2 Certified for Stationary Emergency applications.
What is the fuel consumption of the Generac SDMD2000?
At standby rating on ultra-low-sulfur diesel, the SDMD2000 consumes approximately 140 gallons per hour at 100% load, 105 gph at 75% load, and 70 gph at 50% load. Actual consumption varies by site conditions, load profile, and altitude.
What voltages are available for the SDMD2000?
The SDMD2000 is available in two three-phase configurations: 277/480 VAC and 346/600 VAC, both at 0.8 power factor. The unit is UL 2200 listed and rated at 2,500 kVA standby. Paralleling is supported through Generac's Modular Power Systems (MPS) platform.

Compatible equipment

Similar models

Generac Generac SD1750/MD1750 1.8 MW liquid-cooled standby generator

Generac

Generac SD1750/MD1750

1750 kW mission-critical diesel with Mitsubishi S16R V16 engine. Competitive alternative to CAT 3516 class at lower acquisition cost.

1.8 MW standby · Diesel · Liquid-cooled

1750 kW diesel industrial standby generator. Mitsubishi 65.4L V16 turbocharged/intercooled, EPA Tier 2 Certified Stationary Emergency.

Tier 23-phasecommercial-standbyindustrial
Generac Generac SD2250/MD2250 2.3 MW liquid-cooled standby generator

Generac

Generac SD2250/MD2250

2250 kW diesel in SD/MD platform with Baudouin engine. Competitive alternative to CAT 3516 class at lower cost.

2.3 MW standby · Diesel · Liquid-cooled

2250 kW diesel industrial standby generator. Baudouin 65.6L V12 turbocharged/aftercooled, EPA Tier 2 Certified Stationary Emergency.

Tier 23-phasecommercial-standbyindustrial
Generac Generac SD2500/MD2500 2.5 MW liquid-cooled standby generator

Generac

Generac SD2500/MD2500

2500 kW diesel in SD/MD platform with Baudouin engine. Cost-competitive with CAT 3516B at lower acquisition cost.

2.5 MW standby · Diesel · Liquid-cooled

2500 kW diesel industrial standby generator. Baudouin 65.6L V12 turbocharged/aftercooled, EPA Tier 2 Certified Stationary Emergency. Data Center Ready.

Tier 23-phasecommercial-standbyindustrial

Need service or parts for the Generac SD2000/MD2000?

We service every major OEM and stock genuine parts for the most common models.