Overview#
The DSE 8660 MkII is an auto transfer switch and mains control module — the utility-side controller in a DSE-based multi-generator paralleling system. While the DSE 8610 MkII manages individual generators (one per genset), the 8660 manages the mains/utility connection: monitoring power quality, commanding sync/transfer operations, and providing critical safety functions like mains decoupling protection.
Every DSE-based paralleling installation needs exactly one 8660 (for the mains connection) plus one 8610 per generator.
The paralleling system architecture#
Utility → [DSE 8660 MkII] → Mains Bus
↕ (DSENet communication)
Generator 1 → [DSE 8610 MkII] → Gen Bus ─┐
Generator 2 → [DSE 8610 MkII] → Gen Bus ─┤→ Common Bus → Load
Generator 3 → [DSE 8610 MkII] → Gen Bus ─┘
The 8660 decides:
- When to start generators (mains failure detection)
- When to sync to mains (return-to-mains after outage)
- When to island (mains decoupling on utility loss)
- Load sequencing (which generators start first)
- Export protection (prevent power flowing back to utility)
Key capabilities#
- Forward sync: generators sync to mains for no-break return-to-utility
- Back sync: mains syncs to generators for no-break load pickup
- Sequential set start: brings generators online one at a time (reduces inrush)
- Multiple mains: supports additional 8660 modules for dual-utility-feed systems
- Peak shaving: load management to reduce demand charges
- Integral PLC editor: programmable logic without external PLC
- Redundant DSENet: communication redundancy to genset controllers
Our service experience#
We configure and maintain DSE 8660-based paralleling systems at hospitals and data centers where N+1 redundancy with utility tie is required. The 8660's mains decoupling protection is the critical safety function — it must detect utility loss within cycles and island the generators before backfeed occurs. The DSE Configuration Suite programs both the 8610s and 8660 from one software interface.